- Select Capacity
- Winner Pro Value 1K (L)
- Winner Pro Value 2K (L)
- Winner Pro Value 3K (L)
- Select Capacity
- Winner Pro Value 1K (L)
- Winner Pro Value 2K (L)
- Winner Pro Value 3K (L)
19
Winner Pro Value
Online UPS with a high cost-to-performance ratio
The Winner Pro Value online UPS features a microprocessor controller, making it an intelligent UPS that delivers dependable and consistent power to sensitive devices. Available in capacities from 1000VA to 3000VA, it is perfect for ATMs, banking, and other essential business applications. With an integrated RS-232 port and included monitoring software, this online UPS provides improved power monitoring capabilities.
Main Features
- Genuine double-conversion technology
- Microprocessor-controlled for enhanced reliability
- Input power factor correction
- Output power factor of 0.8
- Broad input voltage range (110 V – 300 V)
- Converter mode option available
- Energy-saving ECO mode
- Compatible with generators
- Intelligent RS-232 communication port
| MODEL | Winner Pro Value 1K (L) | Winner Pro Value 2K (L) | Winner Pro Value 3K (L) | |
| CAPACITY | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | |
| PHASE | Single phase with ground | Single phase with ground | Single phase with ground | |
| INPUT | ||||
| Input Voltage Range | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | |
| Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |
| Frequency Range | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | |
| Power Factor | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | |
| OUTPUT | ||||
| Voltage Regulation | ± 1% | ± 1% | ± 1% | |
| Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | |
| Transfer Time | AC Mode to Battery Mode | Zero | Zero | Zero |
| Transfer Time | Inverter to Bypass | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) |
| Transfer Time | Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave |
| Current Crest Ratio | 3:1 | 3:1 | 3:1 | |
| Harmonic Distortion | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | |
| Frequency Range (Synchronized Range) | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | |
| EFFICIENCY | ||||
| Battery Mode | 83% | 85% | 88% | |
| AC Mode | 88% | 88% | 90% | |
| BATTERY | ||||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries |
| Long-run Model | Charging Current (max.) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4A/6A (Adjustable) |
| Long-run Model | Charging Voltage | 27.4 VDC ± 1%, 41.0 VDC ± 1% | 54.7 VDC ± 1%, 82.1 VDC ± 1%, 109.4 VDC ± 1% | 82.1 VDC ± 1%, 109.4 VDC ± 1% |
| Long-run Model | Numbers | 2, 3 | 4, 6, 8 | 6, 8 |
| Standard Model | Battery Type | 12 V / 9 AH | 12 V / 9 AH | 12 V / 9 AH |
| Standard Model | Charging Current (max.) | 1A | 1A | 1A |
| Standard Model | Charging Voltage | 27.4 VDC ± 1% | 54.7 VDC ± 1% | 82.1 VDC ± 1% |
| Standard Model | Numbers | 2 | 4 | 6 |
| Standard Model | Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
| INDICATORS | ||||
| LED | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | |
| ALARM | ||||
| Battery Mode | Sounding every 4 seconds | Sounding every 4 seconds | Sounding every 4 seconds | |
| Low Battery | Sounding every second | Sounding every second | Sounding every second | |
| Overload | Sounding twice every second | Sounding twice every second | Sounding twice every second | |
| Fault | Continuously sounding | Continuously sounding | Continuously sounding | |
| ENVIRONMENT | ||||
| Operating Humidity | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | |
| Noise Level | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | |
| PHYSICAL | ||||
| Standard Model | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 |
| Standard Model | Net Weight (kgs) | 9.8 | 17 | 27.6 |
| Long-run Model | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 397 x 145 x 220 |
| Long-run Model | Net Weight (kgs) | 4.1 | 6.8 | 7.4 |
| MANAGEMENT | ||||
| Smart RS-232 | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | |
General
CAPACITY
| Winner Pro Value 1K (L) | 1000 VA / 800 W |
|---|---|
| Winner Pro Value 2K (L) | 2000 VA / 1600 W |
| Winner Pro Value 3K (L) | 3000 VA / 2400 W |
PHASE
| Winner Pro Value 1K (L) | Single phase with ground |
|---|---|
| Winner Pro Value 2K (L) | Single phase with ground |
| Winner Pro Value 3K (L) | Single phase with ground |
INPUT
Input Voltage Range
| Winner Pro Value 1K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
|---|---|
| Winner Pro Value 2K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
| Winner Pro Value 3K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
Nominal Voltage
| Winner Pro Value 1K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
|---|---|
| Winner Pro Value 2K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
| Winner Pro Value 3K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Frequency Range
| Winner Pro Value 1K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
|---|---|
| Winner Pro Value 2K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
| Winner Pro Value 3K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
Power Factor
| Winner Pro Value 1K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
|---|---|
| Winner Pro Value 2K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
| Winner Pro Value 3K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
OUTPUT
Voltage Regulation
| Winner Pro Value 1K (L) | ± 1% |
|---|---|
| Winner Pro Value 2K (L) | ± 1% |
| Winner Pro Value 3K (L) | ± 1% |
Output Voltage
| Winner Pro Value 1K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
|---|---|
| Winner Pro Value 2K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
| Winner Pro Value 3K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Frequency Range (Batt. Mode)
| Winner Pro Value 1K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
|---|---|
| Winner Pro Value 2K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
| Winner Pro Value 3K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
Transfer Time AC Mode to Battery Mode
| Winner Pro Value 1K (L) | Zero |
|---|---|
| Winner Pro Value 2K (L) | Zero |
| Winner Pro Value 3K (L) | Zero |
Transfer Time Inverter to Bypass
| Winner Pro Value 1K (L) | 4 ms (Typical) |
|---|---|
| Winner Pro Value 2K (L) | 4 ms (Typical) |
| Winner Pro Value 3K (L) | 4 ms (Typical) |
Transfer Time Waveform (Batt. Mode)
| Winner Pro Value 1K (L) | Pure Sine Wave |
|---|---|
| Winner Pro Value 2K (L) | Pure Sine Wave |
| Winner Pro Value 3K (L) | Pure Sine Wave |
Current Crest Ratio
| Winner Pro Value 1K (L) | 3:1 |
|---|---|
| Winner Pro Value 2K (L) | 3:1 |
| Winner Pro Value 3K (L) | 3:1 |
Harmonic Distortion
| Winner Pro Value 1K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
|---|---|
| Winner Pro Value 2K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
| Winner Pro Value 3K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
Frequency Range (Synchronized Range)
| Winner Pro Value 1K (L) | 47~53 Hz or 57~63 Hz |
|---|---|
| Winner Pro Value 2K (L) | 47~53 Hz or 57~63 Hz |
| Winner Pro Value 3K (L) | 47~53 Hz or 57~63 Hz |
EFFICIENCY
Battery Mode
| Winner Pro Value 1K (L) | 83% |
|---|---|
| Winner Pro Value 2K (L) | 85% |
| Winner Pro Value 3K (L) | 88% |
AC Mode
| Winner Pro Value 1K (L) | 88% |
|---|---|
| Winner Pro Value 2K (L) | 88% |
| Winner Pro Value 3K (L) | 90% |
BATTERY
Long-run Model Battery Type
| Winner Pro Value 1K (L) | Depending on the capacity of external batteries |
|---|---|
| Winner Pro Value 2K (L) | Depending on the capacity of external batteries |
| Winner Pro Value 3K (L) | Depending on the capacity of external batteries |
Long-run Model Charging Current (max.)
| Winner Pro Value 1K (L) | 1A/2A/4A/6A (Adjustable) |
|---|---|
| Winner Pro Value 2K (L) | 1A/2A/4A/6A (Adjustable) |
| Winner Pro Value 3K (L) | 1A/2A/4A/6A (Adjustable) |
Long-run Model Charging Voltage
| Winner Pro Value 1K (L) | 27.4 VDC ± 1%, 41.0 VDC ± 1% |
|---|---|
| Winner Pro Value 2K (L) | 54.7 VDC ± 1%, 82.1 VDC ± 1%, 109.4 VDC ± 1% |
| Winner Pro Value 3K (L) | 82.1 VDC ± 1%, 109.4 VDC ± 1% |
Long-run Model Numbers
| Winner Pro Value 1K (L) | 2, 3 |
|---|---|
| Winner Pro Value 2K (L) | 4, 6, 8 |
| Winner Pro Value 3K (L) | 6, 8 |
Standard Model Battery Type
| Winner Pro Value 1K (L) | 12 V / 9 AH |
|---|---|
| Winner Pro Value 2K (L) | 12 V / 9 AH |
| Winner Pro Value 3K (L) | 12 V / 9 AH |
Standard Model Charging Current (max.)
| Winner Pro Value 1K (L) | 1A |
|---|---|
| Winner Pro Value 2K (L) | 1A |
| Winner Pro Value 3K (L) | 1A |
Standard Model Charging Voltage
| Winner Pro Value 1K (L) | 27.4 VDC ± 1% |
|---|---|
| Winner Pro Value 2K (L) | 54.7 VDC ± 1% |
| Winner Pro Value 3K (L) | 82.1 VDC ± 1% |
Standard Model Numbers
| Winner Pro Value 1K (L) | 2 |
|---|---|
| Winner Pro Value 2K (L) | 4 |
| Winner Pro Value 3K (L) | 6 |
Standard Model Typical Recharge Time
| Winner Pro Value 1K (L) | 4 hours recover to 90% capacity |
|---|---|
| Winner Pro Value 2K (L) | 4 hours recover to 90% capacity |
| Winner Pro Value 3K (L) | 4 hours recover to 90% capacity |
INDICATORS
LED
| Winner Pro Value 1K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
|---|---|
| Winner Pro Value 2K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
| Winner Pro Value 3K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM
Battery Mode
| Winner Pro Value 1K (L) | Sounding every 4 seconds |
|---|---|
| Winner Pro Value 2K (L) | Sounding every 4 seconds |
| Winner Pro Value 3K (L) | Sounding every 4 seconds |
Low Battery
| Winner Pro Value 1K (L) | Sounding every second |
|---|---|
| Winner Pro Value 2K (L) | Sounding every second |
| Winner Pro Value 3K (L) | Sounding every second |
Overload
| Winner Pro Value 1K (L) | Sounding twice every second |
|---|---|
| Winner Pro Value 2K (L) | Sounding twice every second |
| Winner Pro Value 3K (L) | Sounding twice every second |
Fault
| Winner Pro Value 1K (L) | Continuously sounding |
|---|---|
| Winner Pro Value 2K (L) | Continuously sounding |
| Winner Pro Value 3K (L) | Continuously sounding |
ENVIRONMENT
Operating Humidity
| Winner Pro Value 1K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
|---|---|
| Winner Pro Value 2K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
| Winner Pro Value 3K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
Noise Level
| Winner Pro Value 1K (L) | Less than 50dB @ 1 Meter |
|---|---|
| Winner Pro Value 2K (L) | Less than 50dB @ 1 Meter |
| Winner Pro Value 3K (L) | Less than 50dB @ 1 Meter |
PHYSICAL
Standard Model Dimension, D x W x H (mm)
| Winner Pro Value 1K (L) | 282 x 145 x 220 |
|---|---|
| Winner Pro Value 2K (L) | 397 x 145 x 220 |
| Winner Pro Value 3K (L) | 421 x 190 x 318 |
Standard Model Net Weight (kgs)
| Winner Pro Value 1K (L) | 9.8 |
|---|---|
| Winner Pro Value 2K (L) | 17 |
| Winner Pro Value 3K (L) | 27.6 |
Long-run Model Dimension, D x W x H (mm)
| Winner Pro Value 1K (L) | 282 x 145 x 220 |
|---|---|
| Winner Pro Value 2K (L) | 397 x 145 x 220 |
| Winner Pro Value 3K (L) | 397 x 145 x 220 |
Long-run Model Net Weight (kgs)
| Winner Pro Value 1K (L) | 4.1 |
|---|---|
| Winner Pro Value 2K (L) | 6.8 |
| Winner Pro Value 3K (L) | 7.4 |
MANAGEMENT
Smart RS-232
| Winner Pro Value 1K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
|---|---|
| Winner Pro Value 2K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
| Winner Pro Value 3K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
| Brochure | Winner Pro Value 1KVA-3KVA_Brochure | |
| Manual | Winner Pro Value 1KVA-3KVA_Manual |
Single phase - Online UPS Winner Pro Value Online UPS with a high cost-to-performance ratio
Related Products