19
Winner Pro Value
Cost-effective Online UPS
Equipped with microprocessor controller, Winner Pro Value online UPS is a smart UPS providing reliable and stable power performance to sensitive equipment. Ranging from 1000VA to 3000VA, they are ideal for ATMs, banking and other business critical applications. Built-in RS-232 and bundled monitoring software, this online UPS offers enhanced performance for power monitoring.


Main Features
- True double-conversion
- Microprocessor control optimizes reliability
- Input power factor correction
- Output power factor 0.8
- Wide input voltage (110 V – 300 V)
- Converter mode available
- ECO mode for energy saving
- Generator compatible
- Smart RS-232 communication port
MODEL | Winner Pro Value 1K (L) | Winner Pro Value 2K (L) | Winner Pro Value 3K (L) | |
CAPACITY | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | |
PHASE | Single phase with ground | Single phase with ground | Single phase with ground | |
INPUT | ||||
Input Voltage Range | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) | |
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |
Frequency Range | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz | |
Power Factor | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | |
OUTPUT | ||||
Voltage Regulation | ± 1% | ± 1% | ± 1% | |
Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz | |
Transfer Time | AC Mode to Battery Mode | Zero | Zero | Zero |
Transfer Time | Inverter to Bypass | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) |
Transfer Time | Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave |
Current Crest Ratio | 3:1 | 3:1 | 3:1 | |
Harmonic Distortion | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) | |
Frequency Range (Synchronized Range) | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | |
EFFICIENCY | ||||
Battery Mode | 83% | 85% | 88% | |
AC Mode | 88% | 88% | 90% | |
BATTERY | ||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries |
Long-run Model | Charging Current (max.) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4A/6A (Adjustable) |
Long-run Model | Charging Voltage | 27.4 VDC ± 1%, 41.0 VDC ± 1% | 54.7 VDC ± 1%, 82.1 VDC ± 1%, 109.4 VDC ± 1% | 82.1 VDC ± 1%, 109.4 VDC ± 1% |
Long-run Model | Numbers | 2, 3 | 4, 6, 8 | 6, 8 |
Standard Model | Battery Type | 12 V / 9 AH | 12 V / 9 AH | 12 V / 9 AH |
Standard Model | Charging Current (max.) | 1A | 1A | 1A |
Standard Model | Charging Voltage | 27.4 VDC ± 1% | 54.7 VDC ± 1% | 82.1 VDC ± 1% |
Standard Model | Numbers | 2 | 4 | 6 |
Standard Model | Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
INDICATORS | ||||
LED | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | |
ALARM | ||||
Battery Mode | Sounding every 4 seconds | Sounding every 4 seconds | Sounding every 4 seconds | |
Low Battery | Sounding every second | Sounding every second | Sounding every second | |
Overload | Sounding twice every second | Sounding twice every second | Sounding twice every second | |
Fault | Continuously sounding | Continuously sounding | Continuously sounding | |
ENVIRONMENT | ||||
Operating Humidity | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | |
PHYSICAL | ||||
Standard Model | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 |
Standard Model | Net Weight (kgs) | 9.8 | 17 | 27.6 |
Long-run Model | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 397 x 145 x 220 |
Long-run Model | Net Weight (kgs) | 4.1 | 6.8 | 7.4 |
MANAGEMENT | ||||
Smart RS-232 | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
General
CAPACITY
Winner Pro Value 1K (L) | 1000 VA / 800 W |
---|---|
Winner Pro Value 2K (L) | 2000 VA / 1600 W |
Winner Pro Value 3K (L) | 3000 VA / 2400 W |
PHASE
Winner Pro Value 1K (L) | Single phase with ground |
---|---|
Winner Pro Value 2K (L) | Single phase with ground |
Winner Pro Value 3K (L) | Single phase with ground |
INPUT
Input Voltage Range
Winner Pro Value 1K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
---|---|
Winner Pro Value 2K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
Winner Pro Value 3K (L) | 55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%) |
Nominal Voltage
Winner Pro Value 1K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
---|---|
Winner Pro Value 2K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Winner Pro Value 3K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Frequency Range
Winner Pro Value 1K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
---|---|
Winner Pro Value 2K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
Winner Pro Value 3K (L) | 47 Hz ~ 53 Hz or 57 Hz ~ 63 Hz |
Power Factor
Winner Pro Value 1K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
---|---|
Winner Pro Value 2K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
Winner Pro Value 3K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
OUTPUT
Voltage Regulation
Winner Pro Value 1K (L) | ± 1% |
---|---|
Winner Pro Value 2K (L) | ± 1% |
Winner Pro Value 3K (L) | ± 1% |
Output Voltage
Winner Pro Value 1K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
---|---|
Winner Pro Value 2K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Winner Pro Value 3K (L) | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Frequency Range (Batt. Mode)
Winner Pro Value 1K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
---|---|
Winner Pro Value 2K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
Winner Pro Value 3K (L) | 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz |
Transfer Time AC Mode to Battery Mode
Winner Pro Value 1K (L) | Zero |
---|---|
Winner Pro Value 2K (L) | Zero |
Winner Pro Value 3K (L) | Zero |
Transfer Time Inverter to Bypass
Winner Pro Value 1K (L) | 4 ms (Typical) |
---|---|
Winner Pro Value 2K (L) | 4 ms (Typical) |
Winner Pro Value 3K (L) | 4 ms (Typical) |
Transfer Time Waveform (Batt. Mode)
Winner Pro Value 1K (L) | Pure Sine Wave |
---|---|
Winner Pro Value 2K (L) | Pure Sine Wave |
Winner Pro Value 3K (L) | Pure Sine Wave |
Current Crest Ratio
Winner Pro Value 1K (L) | 3:1 |
---|---|
Winner Pro Value 2K (L) | 3:1 |
Winner Pro Value 3K (L) | 3:1 |
Harmonic Distortion
Winner Pro Value 1K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
---|---|
Winner Pro Value 2K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
Winner Pro Value 3K (L) | ≦ 3% THD (Linear Load); ≦ 6% THD (Non-linear Load) |
Frequency Range (Synchronized Range)
Winner Pro Value 1K (L) | 47~53 Hz or 57~63 Hz |
---|---|
Winner Pro Value 2K (L) | 47~53 Hz or 57~63 Hz |
Winner Pro Value 3K (L) | 47~53 Hz or 57~63 Hz |
EFFICIENCY
Battery Mode
Winner Pro Value 1K (L) | 83% |
---|---|
Winner Pro Value 2K (L) | 85% |
Winner Pro Value 3K (L) | 88% |
AC Mode
Winner Pro Value 1K (L) | 88% |
---|---|
Winner Pro Value 2K (L) | 88% |
Winner Pro Value 3K (L) | 90% |
BATTERY
Long-run Model Battery Type
Winner Pro Value 1K (L) | Depending on the capacity of external batteries |
---|---|
Winner Pro Value 2K (L) | Depending on the capacity of external batteries |
Winner Pro Value 3K (L) | Depending on the capacity of external batteries |
Long-run Model Charging Current (max.)
Winner Pro Value 1K (L) | 1A/2A/4A/6A (Adjustable) |
---|---|
Winner Pro Value 2K (L) | 1A/2A/4A/6A (Adjustable) |
Winner Pro Value 3K (L) | 1A/2A/4A/6A (Adjustable) |
Long-run Model Charging Voltage
Winner Pro Value 1K (L) | 27.4 VDC ± 1%, 41.0 VDC ± 1% |
---|---|
Winner Pro Value 2K (L) | 54.7 VDC ± 1%, 82.1 VDC ± 1%, 109.4 VDC ± 1% |
Winner Pro Value 3K (L) | 82.1 VDC ± 1%, 109.4 VDC ± 1% |
Long-run Model Numbers
Winner Pro Value 1K (L) | 2, 3 |
---|---|
Winner Pro Value 2K (L) | 4, 6, 8 |
Winner Pro Value 3K (L) | 6, 8 |
Standard Model Battery Type
Winner Pro Value 1K (L) | 12 V / 9 AH |
---|---|
Winner Pro Value 2K (L) | 12 V / 9 AH |
Winner Pro Value 3K (L) | 12 V / 9 AH |
Standard Model Charging Current (max.)
Winner Pro Value 1K (L) | 1A |
---|---|
Winner Pro Value 2K (L) | 1A |
Winner Pro Value 3K (L) | 1A |
Standard Model Charging Voltage
Winner Pro Value 1K (L) | 27.4 VDC ± 1% |
---|---|
Winner Pro Value 2K (L) | 54.7 VDC ± 1% |
Winner Pro Value 3K (L) | 82.1 VDC ± 1% |
Standard Model Numbers
Winner Pro Value 1K (L) | 2 |
---|---|
Winner Pro Value 2K (L) | 4 |
Winner Pro Value 3K (L) | 6 |
Standard Model Typical Recharge Time
Winner Pro Value 1K (L) | 4 hours recover to 90% capacity |
---|---|
Winner Pro Value 2K (L) | 4 hours recover to 90% capacity |
Winner Pro Value 3K (L) | 4 hours recover to 90% capacity |
INDICATORS
LED
Winner Pro Value 1K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
---|---|
Winner Pro Value 2K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
Winner Pro Value 3K (L) | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM
Battery Mode
Winner Pro Value 1K (L) | Sounding every 4 seconds |
---|---|
Winner Pro Value 2K (L) | Sounding every 4 seconds |
Winner Pro Value 3K (L) | Sounding every 4 seconds |
Low Battery
Winner Pro Value 1K (L) | Sounding every second |
---|---|
Winner Pro Value 2K (L) | Sounding every second |
Winner Pro Value 3K (L) | Sounding every second |
Overload
Winner Pro Value 1K (L) | Sounding twice every second |
---|---|
Winner Pro Value 2K (L) | Sounding twice every second |
Winner Pro Value 3K (L) | Sounding twice every second |
Fault
Winner Pro Value 1K (L) | Continuously sounding |
---|---|
Winner Pro Value 2K (L) | Continuously sounding |
Winner Pro Value 3K (L) | Continuously sounding |
ENVIRONMENT
Operating Humidity
Winner Pro Value 1K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
---|---|
Winner Pro Value 2K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
Winner Pro Value 3K (L) | 20~90% RH @ 0- 40°C (non-condensing) |
Noise Level
Winner Pro Value 1K (L) | Less than 50dB @ 1 Meter |
---|---|
Winner Pro Value 2K (L) | Less than 50dB @ 1 Meter |
Winner Pro Value 3K (L) | Less than 50dB @ 1 Meter |
PHYSICAL
Standard Model Dimension, D x W x H (mm)
Winner Pro Value 1K (L) | 282 x 145 x 220 |
---|---|
Winner Pro Value 2K (L) | 397 x 145 x 220 |
Winner Pro Value 3K (L) | 421 x 190 x 318 |
Standard Model Net Weight (kgs)
Winner Pro Value 1K (L) | 9.8 |
---|---|
Winner Pro Value 2K (L) | 17 |
Winner Pro Value 3K (L) | 27.6 |
Long-run Model Dimension, D x W x H (mm)
Winner Pro Value 1K (L) | 282 x 145 x 220 |
---|---|
Winner Pro Value 2K (L) | 397 x 145 x 220 |
Winner Pro Value 3K (L) | 397 x 145 x 220 |
Long-run Model Net Weight (kgs)
Winner Pro Value 1K (L) | 4.1 |
---|---|
Winner Pro Value 2K (L) | 6.8 |
Winner Pro Value 3K (L) | 7.4 |
MANAGEMENT
Smart RS-232
Winner Pro Value 1K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
---|---|
Winner Pro Value 2K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
Winner Pro Value 3K (L) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
![]() |