Victor 1U 6KL
Lithium UPS featuring a true double-conversion design
The Victor 1U online UPS provides reliable and high-quality power protection to guarantee network and data availability. Each battery pack includes a built-in Battery Management System (BMS) for comprehensive monitoring and management. Its slim 1U design for both the UPS and battery pack saves cabinet space, enabling installation in tighter areas. This compact size also supports longer backup times within a smaller footprint. Compared to traditional lead-acid batteries, the lithium-ion battery lasts 8-10 years—three times longer than VRLA batteries—and typically does not require replacement under normal conditions, lowering the Total Cost of Ownership. Additionally, lithium-ion batteries are lighter and charge more quickly.
Main Features
  • True double-conversion technology
  • Microprocessor control enhances reliability
  • Input power factor correction
  • Output power factor of 0.9
  • Wide input voltage range (110 V – 300 V)
  • Converter mode option available
  • ECO mode for energy efficiency
  • Compatible with generators
  • Advanced SNMP and USB communication
  • Lithium-ion battery module with 10C high discharge rate, high efficiency in a compact 1U size
  • Built-in Wi-Fi with an app for remote monitoring
  • Comprehensive display for easy UPS monitoring and access
General
CAPACITY
Victor 1U 6KL600VA/5400W
PHASE
Victor 1U 6KLSingle phase(L+N+PE)
INPUT
Voltage Range
Victor 1U 6KL110-300VAC±3% at50% load;176-300VAC ±3% at 100% load
Nominal Voltage
Victor 1U 6KL208*/220/230/240VAC
Frequency Range
Victor 1U 6KL46~54Hz / 56~64 Hz
Power Factor
Victor 1U 6KL≧0.99 @ nominal voltage (100% load)
THDi
Victor 1U 6KL≦4% @100% load
OUTPUT
Voltage Regulation
Victor 1U 6KL± 1%
Output Voltage
Victor 1U 6KL208*/220/230/240VAC
Transfer Time AC Mode to Battery Mode
Victor 1U 6KLZero
Transfer Time Inverter to Bypass
Victor 1U 6KL≦4 ms (Typical)
Waveform (Batt. Mode)
Victor 1U 6KLPure Sine Wave
Current Crest Ratio
Victor 1U 6KL3:1(max.)
Harmonic Distortion
Victor 1U 6KL≦2%THD(Linear Load)/4%THD (Non-linear Load)
Frequency Range (Synchronized Range)
Victor 1U 6KL46~54Hz / 56~64 Hz
Overload AC Mode
Victor 1U 6KL100%≦ load≦105%Warning only:105%<load≦125% 1min:>125%:1sec
Overload Battery Mode
Victor 1U 6KL100%≦ load≦105%Warning only:105%<load≦125% 30 sec:>125%:1sec
EFFICIENCY
Battery Mode
Victor 1U 6KL93%(max.)
AC Mode
Victor 1U 6KL95%(max.)
BATTERY
Charging Current
Victor 1U 6KL6.0A(max.)
Charging Voltage
Victor 1U 6KL210VDC±1%
Nominal Voltage
Victor 1U 6KL192VDC
Battery Connector
Victor 1U 6KL2 Poles(50A max.)
ENVIRONMENT
Altitude
Victor 1U 6KL0~2000meters without derating;2000~3000 meters,derating 1% every 100 meters;>3000 meters, not working
Noise Level
Victor 1U 6KLLess than 55dBA @ 1 Meter
Humidity
Victor 1U 6KL0~95% RH @ 0- 40°C (non-condensing)
PHYSICAL
Dimension, D X W X H (mm)
Victor 1U 6KL550 X 438 X 44
Net Weight (kgs)
Victor 1U 6KL9.5
MANAGEMENT
Optional SNMP
Victor 1U 6KL Power management from SNMP manager and web browser
USB
Victor 1U 6KLSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux and MAC
Optional WiFi module
Victor 1U 6KLAPP for Wifi linking
INDICATORS & COM
LCD
Victor 1U 6KLLoad level, Battery level,AC mode, Battery modeand fault indicators
Communication ports
Victor 1U 6KLUSB, Mini Slot,WiFi
Emergency Power Off (EPO)
Victor 1U 6KLYES
EXTERNAL LITHIUM-ION BATTERY MODULE
Model Name
Victor 1U 6KLLIO 192003
Capacity
Victor 1U 6KL3Ah
Nominal DC Voltage
Victor 1U 6KL192VDC
Cell Type and nominal capacity
Victor 1U 6KLLiFeO4 and 3.2V/3Ah
continuous Discharge Current
Victor 1U 6KL30A max.
Battery Connector
Victor 1U 6KL2 Poles(50A max.)
Com Ports
Victor 1U 6KLRS485(Pack to UPS),CAN(pack to pack)
capacity Extension
Victor 1U 6KLYES, max up to 3 packs
Dimension, D X W X H (mm)
Victor 1U 6KL550 X 438 X 44
Net Weight (kgs)
Victor 1U 6KL15.5
Backup Time
Victor 1U 6KL5400W @ 4 min. / 4800W @ 6 min.