Solar Online UPS 1KVA-3KVA
Online UPS integrated with a solar charger
The Solar Online UPS 1KVA-3KVA comes equipped with an integrated MPPT solar charger and smart SBU (Solar, Battery, Utility) priority management. This allows for direct connection of solar panels to the UPS, making utility power just one of several power sources. When grid power is unavailable, the UPS will use solar energy to charge the battery. With the SBU priority smart management feature, you can customize the priority of the UPS’s energy sources according to your preferences. Additionally, the charger capacity can be increased up to 6A to reduce charging time.
Main Features
  • SBU (Solar, Battery, Utility) Priority Intelligent Management
  • Equipped with a built-in 1KW or 1.5KW MPPT solar charger
  • Features true double-conversion technology
  • Includes input power factor correction
  • Supports a wide input voltage range (110V-280V)
  • Offers converter mode functionality
  • Energy-saving ECO mode available
  • Compatible with generators
  • An optional isolation transformer provides full isolation and effective common-mode noise rejection
  • Comprehensive display enables easy monitoring and convenient access to UPS and solar energy status
General
CAPACITY
SOLAR UPS 1KW1000 VA / 800 W
SOLAR UPS 2KW2000 VA / 1600 W
SOLAR UPS 3KW3000 VA / 2400 W
INPUT
Voltage
SOLAR UPS 1KW220/230/240VAC
SOLAR UPS 2KW220/230/240VAC
SOLAR UPS 3KW220/230/240VAC
Voltage Range
SOLAR UPS 1KW110-280 VAC
SOLAR UPS 2KW110-280 VAC
SOLAR UPS 3KW110-280 VAC
Frequency Range
SOLAR UPS 1KW40 Hz-70 Hz
SOLAR UPS 2KW40 Hz-70 Hz
SOLAR UPS 3KW40 Hz-70 Hz
Power Factor
SOLAR UPS 1KW≧ 0.95 @ Nominal Voltage (100% Load)
SOLAR UPS 2KW≧ 0.95 @ Nominal Voltage (100% Load)
SOLAR UPS 3KW≧ 0.95 @ Nominal Voltage (100% Load)
OUTPUT
AC Voltage Regulation (Batt. Mode)
SOLAR UPS 1KW220/230/240VAC
SOLAR UPS 2KW220/230/240VAC
SOLAR UPS 3KW220/230/240VAC
Frequency Range (Batt. Mode)
SOLAR UPS 1KW50 Hz or 60Hz ± 0.1 Hz
SOLAR UPS 2KW50 Hz or 60Hz ± 0.1 Hz
SOLAR UPS 3KW50 Hz or 60Hz ± 0.1 Hz
Transfer Time AC Mode to Batt. Mode
SOLAR UPS 1KWZero
SOLAR UPS 2KWZero
SOLAR UPS 3KWZero
Transfer Time Inverter to Bypass
SOLAR UPS 1KW4 ms (Typical)
SOLAR UPS 2KW4 ms (Typical)
SOLAR UPS 3KW4 ms (Typical)
Waveform
SOLAR UPS 1KWPure Sinewave
SOLAR UPS 2KWPure Sinewave
SOLAR UPS 3KWPure Sinewave
Harmonic Distortion
SOLAR UPS 1KW≦ 3% THD (Linear Load) ; ≦ 6 % THD (Non-linear Load)
SOLAR UPS 2KW≦ 3% THD (Linear Load) ; ≦ 6 % THD (Non-linear Load)
SOLAR UPS 3KW≦ 3% THD (Linear Load) ; ≦ 6 % THD (Non-linear Load)
Frequency Range (Synchronized Range)
SOLAR UPS 1KW47~ 53 Hz or 57 ~ 63 Hz
SOLAR UPS 2KW47~ 53 Hz or 57 ~ 63 Hz
SOLAR UPS 3KW47~ 53 Hz or 57 ~ 63 Hz
EFFICIENCY
Battery Mode
SOLAR UPS 1KW0.83
SOLAR UPS 2KW0.87
SOLAR UPS 3KW0.88
Line Mode
SOLAR UPS 1KW0.88
SOLAR UPS 2KW0.89
SOLAR UPS 3KW0.9
BATTERY
Battery Voltage
SOLAR UPS 1KW36Vdc
SOLAR UPS 2KW72Vdc
SOLAR UPS 3KW72Vdc
Charging Voltage
SOLAR UPS 1KW41.0VDC ± 1%
SOLAR UPS 2KW82.1VDC ± 1%
SOLAR UPS 3KW82.1VDC ± 1%
Charging Current (max.)
SOLAR UPS 1KW1/2/4/6A(Default), adjustable by internal jumper
SOLAR UPS 2KW1/2/4/6A(Default), adjustable by internal jumper
SOLAR UPS 3KW1/2/4/6A(Default), adjustable by internal jumper
SOLAR CHARGER & AC CHARGER
Solar Charger Type
SOLAR UPS 1KWMPPT
SOLAR UPS 2KWMPPT
SOLAR UPS 3KWMPPT
Maximum PV Array Open Circuit Voltage
SOLAR UPS 1KW145 VDC
SOLAR UPS 2KW145 VDC
SOLAR UPS 3KW145 VDC
Maximum PV Array Power
SOLAR UPS 1KW1000W
SOLAR UPS 2KW1500W
SOLAR UPS 3KW1500W
MPPT Range @ Operating Voltage
SOLAR UPS 1KW40 VDC - 115 VDC
SOLAR UPS 2KW90 VDC - 115 VDC
SOLAR UPS 3KW90 VDC - 115 VDC
Maximum AC Charge Current
SOLAR UPS 1KW20A
SOLAR UPS 2KW20A
SOLAR UPS 3KW20A
Maximum Charging Current
SOLAR UPS 1KW15A
SOLAR UPS 2KW15A
SOLAR UPS 3KW15A
PHYSICAL
Dimension, D X W X H (mm)
SOLAR UPS 1KW282 x 145 x 332
SOLAR UPS 2KW400 x 145 x 332
SOLAR UPS 3KW400 x145x332
Net Weight (kgs)
SOLAR UPS 1KW7.6
SOLAR UPS 2KW12
SOLAR UPS 3KW12.3
Communication Port
SOLAR UPS 1KWRS232 & USB
SOLAR UPS 2KWRS232 & USB
SOLAR UPS 3KWRS232 & USB
OPERATING ENVIRONMENT
Operating Humidity
SOLAR UPS 1KW20-90 % RH @ 0- 50°C (non-condensing)
SOLAR UPS 2KW20-90 % RH @ 0- 50°C (non-condensing)
SOLAR UPS 3KW20-90 % RH @ 0- 50°C (non-condensing)
Brochure Solar Online UPS 1KVA-3KVA Brochure