- Select Capacity
- InfiniSolar WP 30KW
- InfiniSolar WP 50KW
- Select Capacity
- InfiniSolar WP 30KW
- InfiniSolar WP 50KW
198
InfiniSolar WP 30KW, 50KW
3-phase IP65 hybrid solar inverter with dual AC input power sources
With Ingress protection to IP65, InfiniSolar WP 30kW & 50kW is suitable for use both in outdoor applications and indoor environments where atmospheric moisture and dust are present. InfiniSolar WP 30kW & 50kW also offers a dual AC input power source compatible with generator power to guarantee uninterruptible power. It allows parallel operation up to 4 units for power expansion.


Main Features
- IP65 waterproof and dustproof makes the inverter available for various working conditions
- Built-in third generation SIC MOSFET improves efficiency
- Dual AC inputs for Generator and Utility input compatible
- Built-in WiFi for mobile monitoring (App is available)
- Enhance AC/Solar charger to 50A
- Wide battery input range
- Built-in communication port for BMS (RS485)
- 5 years warranty
- Parallel operation of up to 4 units
MODEL | InfiniSolar WP 30KW | InfiniSolar WP 50KW | |
PHASE | 3-phase in/3-phase out | 3-phase in/3-phase out | |
Maximum PV Input Power | 40000 W | 65000 W | |
Rated Output Power | 30000 W | 50000 W | |
Maximum Charging Power | 30000 W | 50000 W | |
GRID-TIE OPERATION | |||
PV INPUT (DC) | |||
Nominal DC Voltage / Maximum DC Voltage | 720 VDC / 1000 VDC | 720 VDC / 1000 VDC | |
Start-up Voltage / Initial Feeding Voltage | 320 VDC / 350 VDC | 320 VDC / 350 VDC | |
Number of MPP Trackers/Max. Input Current | 3 / A: 26A, B: 26A, C: 26A | 4 / A: 32A, B: 32A, C: 32A, D: 32A | |
MPP Voltage Range | 350 VDC ~ 900 VDC | 350 VDC ~ 900 VDC | |
Number of Strings Per MPP Tracker | A: 2, B: 2, C: 2 | A: 2, B: 2, C: 2, D: 2 | |
GRID OUTPUT (AC) | |||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Voltage Range | 184 - 265 VAC per phase | 184 - 265 VAC per phase | |
Nominal Output Current | 43.5 A per phase | 73 A per phase | |
Power Factor | 0.9 lag ~ 0.9 lead | 0.9 lag ~ 0.9 lead | |
EFFICIENCY | |||
Maximum Conversion Efficiency (DC/AC) | 96.5% | 96.5% | |
European Efficiency@ Vnominal | 96% | 96% | |
OFF-GRID OPERATION | |||
AC INPUT | |||
AC Start-up Voltage / Auto Restart Voltage | 120 - 140 VAC /180 VAC per phase | 120 - 140 VAC /180 VAC per phase | |
Acceptable Voltage Range | 170 - 280 VAC per phase | 170 - 280 VAC per phase | |
Maximum AC Input Current | 50 A | 83 A | |
PV INPUT (DC) | |||
Maximum DC Voltage | 1000 VDC | 1000 VDC | |
Number of MPP Trackers/Max. Input Current | 3 / A: 26A, B: 26A, C: 26A | 4 / A: 32A, B: 32A, C: 32A, D: 32A | |
MPP Voltage Range | 350 VDC ~ 900 VDC | 350 VDC ~ 900 VDC | |
BATTERY MODE OUTPUT (AC) | |||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Waveform | Pure sine wave | Pure sine wave | |
HYBRID OPERATION | |||
PV INPUT (DC) | |||
Start-up Voltage / Initial Feeding Voltage | 320 VDC / 350 VDC | 320 VDC / 350 VDC | |
Number of MPP Trackers/Max. Input Current | 3 / A: 26A, B: 26A, C: 26A | 4 / A: 32A, B: 32A, C: 32A, D: 32A | |
MPP Voltage Range | 350 VDC ~ 900 VDC | 350 VDC ~ 900 VDC | |
Maximum DC Voltage | 1000 VDC | 1000 VDC | |
GRID OUTPUT (AC) | |||
Nominal Output Current | 43.5 A per phase | 73 A per phase | |
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | 230 VAC (P-N) / 400 VAC (P-P) | |
Output Voltage Range | 184 - 265 VAC per phase | 184 - 265 VAC per phase | |
AC INPUT | |||
AC Start-up Voltage / Auto Restart Voltage | 120 - 140 VAC /180 VAC per phase | 120 - 140 VAC /180 VAC per phase | |
Acceptable Voltage Range | 170 - 280 VAC per phase | 170 - 280 VAC per phase | |
Maximum AC Input Current | 50 A | 83 A | |
BATTERY MODE OUTPUT (AC) | |||
Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | 230 VAC (P-N) / 400 VAC (P-P) | |
Efficiency (DC to AC) | 97% | 97% | |
BATTERY & CHARGER | |||
Maximum Charging Current | 50 A | 65 A | |
Battery Voltage Range | 500 ~ 900 VDC | 500 ~ 800 VDC | |
GENERAL | |||
PHYSICAL | |||
Dimension, D X W X H (mm) | 255 x 660 x 750 | 268 x 660 x 750 | |
Net Weight (kgs) | 73 | 110 | |
INTERFACE | |||
Communication Port | RS-232, USB, DRY CONTACT, RS-485 and Wi-Fi | RS-232, USB, DRY CONTACT, RS-485, CAN, Bluetooth, and Wi-Fi | |
Intelligent Slot | Optional SNMP, Modbus and GPRS cards | Optional SNMP, Modbus and GPRS cards | |
ENVIRONMENT | |||
Humidity | 0 ~ 100% RH (Non-condensing) | 0 ~ 100% RH (Non-condensing) | |
Operating Temperature | -25 to 60°C, > 45°C power derating | -25 to 60°C, > 45°C power derating | |
Altitude | 0 ~ 1000 m** | 0 ~ 1000 m** |
MODEL
General
PHASE
InfiniSolar WP 30KW | 3-phase in/3-phase out |
---|---|
InfiniSolar WP 50KW | 3-phase in/3-phase out |
Maximum PV Input Power
InfiniSolar WP 30KW | 40000 W |
---|---|
InfiniSolar WP 50KW | 65000 W |
Rated Output Power
InfiniSolar WP 30KW | 30000 W |
---|---|
InfiniSolar WP 50KW | 50000 W |
Maximum Charging Power
InfiniSolar WP 30KW | 30000 W |
---|---|
InfiniSolar WP 50KW | 50000 W |
GRID-TIE OPERATION
PV INPUT (DC)
Nominal DC Voltage / Maximum DC Voltage
InfiniSolar WP 30KW | 720 VDC / 1000 VDC |
---|---|
InfiniSolar WP 50KW | 720 VDC / 1000 VDC |
Start-up Voltage / Initial Feeding Voltage
InfiniSolar WP 30KW | 320 VDC / 350 VDC |
---|---|
InfiniSolar WP 50KW | 320 VDC / 350 VDC |
Number of MPP Trackers/Max. Input Current
InfiniSolar WP 30KW | 3 / A: 26A, B: 26A, C: 26A |
---|---|
InfiniSolar WP 50KW | 4 / A: 32A, B: 32A, C: 32A, D: 32A |
MPP Voltage Range
InfiniSolar WP 30KW | 350 VDC ~ 900 VDC |
---|---|
InfiniSolar WP 50KW | 350 VDC ~ 900 VDC |
Number of Strings Per MPP Tracker
InfiniSolar WP 30KW | A: 2, B: 2, C: 2 |
---|---|
InfiniSolar WP 50KW | A: 2, B: 2, C: 2, D: 2 |
GRID OUTPUT (AC)
Nominal Output Voltage
InfiniSolar WP 30KW | 230 VAC (P-N) / 400 VAC (P-P) |
---|---|
InfiniSolar WP 50KW | 230 VAC (P-N) / 400 VAC (P-P) |
Output Voltage Range
InfiniSolar WP 30KW | 184 - 265 VAC per phase |
---|---|
InfiniSolar WP 50KW | 184 - 265 VAC per phase |
Nominal Output Current
InfiniSolar WP 30KW | 43.5 A per phase |
---|---|
InfiniSolar WP 50KW | 73 A per phase |
Power Factor
InfiniSolar WP 30KW | 0.9 lag ~ 0.9 lead |
---|---|
InfiniSolar WP 50KW | 0.9 lag ~ 0.9 lead |
EFFICIENCY
Maximum Conversion Efficiency (DC/AC)
InfiniSolar WP 30KW | 96.5% |
---|---|
InfiniSolar WP 50KW | 96.5% |
European Efficiency@ Vnominal
InfiniSolar WP 30KW | 96% |
---|---|
InfiniSolar WP 50KW | 96% |
OFF-GRID OPERATION
AC INPUT
AC Start-up Voltage / Auto Restart Voltage
InfiniSolar WP 30KW | 120 - 140 VAC /180 VAC per phase |
---|---|
InfiniSolar WP 50KW | 120 - 140 VAC /180 VAC per phase |
Acceptable Voltage Range
InfiniSolar WP 30KW | 170 - 280 VAC per phase |
---|---|
InfiniSolar WP 50KW | 170 - 280 VAC per phase |
Maximum AC Input Current
InfiniSolar WP 30KW | 50 A |
---|---|
InfiniSolar WP 50KW | 83 A |
PV INPUT (DC)
Maximum DC Voltage
InfiniSolar WP 30KW | 1000 VDC |
---|---|
InfiniSolar WP 50KW | 1000 VDC |
Number of MPP Trackers/Max. Input Current
InfiniSolar WP 30KW | 3 / A: 26A, B: 26A, C: 26A |
---|---|
InfiniSolar WP 50KW | 4 / A: 32A, B: 32A, C: 32A, D: 32A |
MPP Voltage Range
InfiniSolar WP 30KW | 350 VDC ~ 900 VDC |
---|---|
InfiniSolar WP 50KW | 350 VDC ~ 900 VDC |
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage
InfiniSolar WP 30KW | 230 VAC (P-N) / 400 VAC (P-P) |
---|---|
InfiniSolar WP 50KW | 230 VAC (P-N) / 400 VAC (P-P) |
Output Waveform
InfiniSolar WP 30KW | Pure sine wave |
---|---|
InfiniSolar WP 50KW | Pure sine wave |
HYBRID OPERATION
PV INPUT (DC)
Start-up Voltage / Initial Feeding Voltage
InfiniSolar WP 30KW | 320 VDC / 350 VDC |
---|---|
InfiniSolar WP 50KW | 320 VDC / 350 VDC |
Number of MPP Trackers/Max. Input Current
InfiniSolar WP 30KW | 3 / A: 26A, B: 26A, C: 26A |
---|---|
InfiniSolar WP 50KW | 4 / A: 32A, B: 32A, C: 32A, D: 32A |
MPP Voltage Range
InfiniSolar WP 30KW | 350 VDC ~ 900 VDC |
---|---|
InfiniSolar WP 50KW | 350 VDC ~ 900 VDC |
Maximum DC Voltage
InfiniSolar WP 30KW | 1000 VDC |
---|---|
InfiniSolar WP 50KW | 1000 VDC |
GRID OUTPUT (AC)
Nominal Output Current
InfiniSolar WP 30KW | 43.5 A per phase |
---|---|
InfiniSolar WP 50KW | 73 A per phase |
Nominal Output Voltage
InfiniSolar WP 30KW | 230 VAC (P-N) / 400 VAC (P-P) |
---|---|
InfiniSolar WP 50KW | 230 VAC (P-N) / 400 VAC (P-P) |
Output Voltage Range
InfiniSolar WP 30KW | 184 - 265 VAC per phase |
---|---|
InfiniSolar WP 50KW | 184 - 265 VAC per phase |
AC INPUT
AC Start-up Voltage / Auto Restart Voltage
InfiniSolar WP 30KW | 120 - 140 VAC /180 VAC per phase |
---|---|
InfiniSolar WP 50KW | 120 - 140 VAC /180 VAC per phase |
Acceptable Voltage Range
InfiniSolar WP 30KW | 170 - 280 VAC per phase |
---|---|
InfiniSolar WP 50KW | 170 - 280 VAC per phase |
Maximum AC Input Current
InfiniSolar WP 30KW | 50 A |
---|---|
InfiniSolar WP 50KW | 83 A |
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage
InfiniSolar WP 30KW | 230 VAC (P-N) / 400 VAC (P-P) |
---|---|
InfiniSolar WP 50KW | 230 VAC (P-N) / 400 VAC (P-P) |
Efficiency (DC to AC)
InfiniSolar WP 30KW | 97% |
---|---|
InfiniSolar WP 50KW | 97% |
BATTERY & CHARGER
Maximum Charging Current
InfiniSolar WP 30KW | 50 A |
---|---|
InfiniSolar WP 50KW | 65 A |
Battery Voltage Range
InfiniSolar WP 30KW | 500 ~ 900 VDC |
---|---|
InfiniSolar WP 50KW | 500 ~ 800 VDC |
GENERAL
PHYSICAL
Dimension, D X W X H (mm)
InfiniSolar WP 30KW | 255 x 660 x 750 |
---|---|
InfiniSolar WP 50KW | 268 x 660 x 750 |
Net Weight (kgs)
InfiniSolar WP 30KW | 73 |
---|---|
InfiniSolar WP 50KW | 110 |
INTERFACE
Communication Port
InfiniSolar WP 30KW | RS-232, USB, DRY CONTACT, RS-485 and Wi-Fi |
---|---|
InfiniSolar WP 50KW | RS-232, USB, DRY CONTACT, RS-485, CAN, Bluetooth, and Wi-Fi |
Intelligent Slot
InfiniSolar WP 30KW | Optional SNMP, Modbus and GPRS cards |
---|---|
InfiniSolar WP 50KW | Optional SNMP, Modbus and GPRS cards |
ENVIRONMENT
Humidity
InfiniSolar WP 30KW | 0 ~ 100% RH (Non-condensing) |
---|---|
InfiniSolar WP 50KW | 0 ~ 100% RH (Non-condensing) |
Operating Temperature
InfiniSolar WP 30KW | -25 to 60°C, > 45°C power derating |
---|---|
InfiniSolar WP 50KW | -25 to 60°C, > 45°C power derating |
Altitude
InfiniSolar WP 30KW | 0 ~ 1000 m** |
---|---|
InfiniSolar WP 50KW | 0 ~ 1000 m** |
![]() |
Brochure | InfiniSolarWP-30KW_DS |
![]() |
Manual | InfiniSolar WP 30K Manual |
On-Grid with Energy-Storage Inverter InfiniSolar WP 30KW, 50KW 3-phase IP65 hybrid solar inverter with dual AC input power sources
Related Products