Giant II 33 10KVA-160KVA
3-Phase Online UPS Integrated with an Isolation Transformer
Equipped with an isolation transformer, the Giant series effectively removes common mode noise and eliminates the requirement for costly specialized circuits. It delivers dependable galvanic isolation power to essential devices.
Main Features
- True online double conversion with DSP control
- Output power factor of 0.9, customizable up to 1.0
- Galvanic isolation eliminates common-mode noise, delivering the cleanest power even in the most demanding conditions
- Conformal coating ensures stable and safe operation in critical environments
- Standard IP31 protection, with an optional IP42 rating for harsher environments
- Supports long-term operation for all types of loads, even under low input voltage
- Redundant design to ensure product reliability
- Temperature compensation to extend battery lifespan
- Equipped with backfeed protection for safe operation
- 7-inch touch color LCD featuring customizable control settings and easy access to UPS information
- Supports dual-mains input
- Parallel capability for up to 4 units
- An optional 40kA surge protection module is available
- An optional FOOTMASTER caster wheel is available
| MODEL | Giant II 10K | Giant II 15K | Giant II 20K | Giant II 30K | Giant II 40K | Giant II 60K | |
| CAPACITY | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | 30KVA/27KW | 40KVA/36KW | 60KVA/54KW | |
| INPUT | |||||||
| Nominal Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| Acceptable Voltage Range | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | |
| Frequency | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | |
| Rectifier Type | 6 pulse | 6 pulse | 6 pulse | 6 pulse | 6 pulse | 6 pulse | |
| Main Input and Bypass Input | Supports dual inputs | Supports dual inputs | Supports dual inputs | Supports dual inputs | Supports dual inputs | Supports dual inputs | |
| TVSS | 40kA (optional) | 40kA (optional) | 40kA (optional) | 40kA (optional) | 40kA (optional) | 40kA (optional) | |
| OUTPUT | |||||||
| Overload Capability | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | |
| Power Factor | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | |
| Nominal Output Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| Output Voltage Regulation | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% | |
| BYPASS | |||||||
| Input Voltage Range | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | |
| Nominal Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| BATTERY | |||||||
| Battery Voltage | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | |
| Cold Start | Yes | Yes | Yes | Yes | Yes | Yes | |
| ENVIRONMENT | |||||||
| Altitude | 1000m | 1000m | 1000m | 1000m | 1000m | 1000m | |
| Operating Temperature | 0~ 50°C | 0~ 50°C | 0~ 50°C | 0~ 50°C | 0~ 50°C | 0~ 50°C | |
| Humidity | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | |
| Storage Temperature | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | |
| PHYSICAL | |||||||
| Net Weight (Kgs) | 120 | 145 | 193 | 278 | 365 | 471 | |
| IP Protection | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | |
| Dimensions, D x W x H(mm) | 656 x 405 x 817 | 656 x 405 x 817 | 656 x 405 x 941 | 821 x 432 x 1159 | 821 x 432 x 1159 | 800 x 1200 x 1800 | |
| MANAGEMENT | |||||||
| Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
| Modbus RS-232 / RS485 | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | |
| Dry Contacts | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | |
| STANDARD | |||||||
| Safety | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | |
| Model | Giant II 80K | Giant II 100K | Giant II 120K | Giant II 160K | |
| CAPACITY | 80KVA/72KW | 100KVA/90KW | 120KVA/108KW | 160KVA/144KW | |
| INPUT | |||||
| Nominal Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| Acceptable Voltage Range | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | 304VAC ~ 456VAC | |
| Frequency | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | 50Hz ± 10% | |
| Rectifier Type | 6 pulse | 12 pulse | 12 pulse | 12 pulse | |
| Main Input and Bypass Input | Supports dual inputs | Supports dual inputs | Supports dual inputs | Supports dual inputs | |
| TVSS | 40kA (optional) | 40kA (optional) | 40kA (optional) | 40kA (optional) | |
| OUTPUT | |||||
| Overload Capability | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | 110% continuous running; 125% for 10 min; >150% for 1 min | |
| Power Factor | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | 0.9, customized up to 1.0 | |
| Nominal Output Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| Output Voltage Regulation | ±1% | ±1% | ±1% | ±1% | |
| BYPASS | |||||
| Input Voltage Range | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | 285VAC ~ 475VAC | |
| Nominal Voltage | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | 380VAC/400VAC/415VAC | |
| BATTERY | |||||
| Battery Voltage | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | 384 VDC (Adjustable) | |
| Cold Start | Yes | Yes | Yes | Yes | |
| ENVIRONMENT | |||||
| Altitude | 1000m | 1000m | 1000m | 1000m | |
| Operating Temperature | 0~ 50°C | 0~ 50°C | 0~ 50°C | 0~ 50°C | |
| Humidity | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) | |
| Storage Temperature | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | -25°C ~ 55°C | |
| PHYSICAL | |||||
| Net Weight (Kgs) | 573 | 650 | 735 | 790 | |
| IP Protection | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | IP31 (default), IP42 (optional) | |
| Dimensions, D x W x H(mm) | 800 x 1200 x 1800 | 975 x 635 x 1326 | 1051x705x1646 | 1051x705x1646 | |
| MANAGEMENT | |||||
| Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
| Modbus RS-232 / RS485 | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | Supports Windows® family, Linux and MAC | |
| Dry Contacts | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | 5 outputs and 4 inputs | |
| STANDARD | |||||
| Safety | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | IEC62040-1-2017 | |
General
CAPACITY
| Giant II 10K | 10KVA/9KW |
|---|---|
| Giant II 15K | 15KVA/13.5KW |
| Giant II 20K | 20KVA/18KW |
| Giant II 30K | 30KVA/27KW |
| Giant II 40K | 40KVA/36KW |
| Giant II 60K | 60KVA/54KW |
| Giant II 80K | 80KVA/72KW |
| Giant II 100K | 100KVA/90KW |
| Giant II 120K | 120KVA/108KW |
| Giant II 160K | 160KVA/144KW |
INPUT
Nominal Voltage
| Giant II 10K | 380VAC/400VAC/415VAC |
|---|---|
| Giant II 15K | 380VAC/400VAC/415VAC |
| Giant II 20K | 380VAC/400VAC/415VAC |
| Giant II 30K | 380VAC/400VAC/415VAC |
| Giant II 40K | 380VAC/400VAC/415VAC |
| Giant II 60K | 380VAC/400VAC/415VAC |
| Giant II 80K | 380VAC/400VAC/415VAC |
| Giant II 100K | 380VAC/400VAC/415VAC |
| Giant II 120K | 380VAC/400VAC/415VAC |
| Giant II 160K | 380VAC/400VAC/415VAC |
Acceptable Voltage Range
| Giant II 10K | 304VAC ~ 456VAC |
|---|---|
| Giant II 15K | 304VAC ~ 456VAC |
| Giant II 20K | 304VAC ~ 456VAC |
| Giant II 30K | 304VAC ~ 456VAC |
| Giant II 40K | 304VAC ~ 456VAC |
| Giant II 60K | 304VAC ~ 456VAC |
| Giant II 80K | 304VAC ~ 456VAC |
| Giant II 100K | 304VAC ~ 456VAC |
| Giant II 120K | 304VAC ~ 456VAC |
| Giant II 160K | 304VAC ~ 456VAC |
Frequency
| Giant II 10K | 50Hz ± 10% |
|---|---|
| Giant II 15K | 50Hz ± 10% |
| Giant II 20K | 50Hz ± 10% |
| Giant II 30K | 50Hz ± 10% |
| Giant II 40K | 50Hz ± 10% |
| Giant II 60K | 50Hz ± 10% |
| Giant II 80K | 50Hz ± 10% |
| Giant II 100K | 50Hz ± 10% |
| Giant II 120K | 50Hz ± 10% |
| Giant II 160K | 50Hz ± 10% |
Rectifier Type
| Giant II 10K | 6 pulse |
|---|---|
| Giant II 15K | 6 pulse |
| Giant II 20K | 6 pulse |
| Giant II 30K | 6 pulse |
| Giant II 40K | 6 pulse |
| Giant II 60K | 6 pulse |
| Giant II 80K | 6 pulse |
| Giant II 100K | 12 pulse |
| Giant II 120K | 12 pulse |
| Giant II 160K | 12 pulse |
Main Input and Bypass Input
| Giant II 10K | Supports dual inputs |
|---|---|
| Giant II 15K | Supports dual inputs |
| Giant II 20K | Supports dual inputs |
| Giant II 30K | Supports dual inputs |
| Giant II 40K | Supports dual inputs |
| Giant II 60K | Supports dual inputs |
| Giant II 80K | Supports dual inputs |
| Giant II 100K | Supports dual inputs |
| Giant II 120K | Supports dual inputs |
| Giant II 160K | Supports dual inputs |
TVSS
| Giant II 10K | 40kA (optional) |
|---|---|
| Giant II 15K | 40kA (optional) |
| Giant II 20K | 40kA (optional) |
| Giant II 30K | 40kA (optional) |
| Giant II 40K | 40kA (optional) |
| Giant II 60K | 40kA (optional) |
| Giant II 80K | 40kA (optional) |
| Giant II 100K | 40kA (optional) |
| Giant II 120K | 40kA (optional) |
| Giant II 160K | 40kA (optional) |
OUTPUT
Overload Capability
| Giant II 10K | 110% continuous running; 125% for 10 min; >150% for 1 min |
|---|---|
| Giant II 15K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 20K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 30K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 40K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 60K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 80K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 100K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 120K | 110% continuous running; 125% for 10 min; >150% for 1 min |
| Giant II 160K | 110% continuous running; 125% for 10 min; >150% for 1 min |
Power Factor
| Giant II 10K | 0.9, customized up to 1.0 |
|---|---|
| Giant II 15K | 0.9, customized up to 1.0 |
| Giant II 20K | 0.9, customized up to 1.0 |
| Giant II 30K | 0.9, customized up to 1.0 |
| Giant II 40K | 0.9, customized up to 1.0 |
| Giant II 60K | 0.9, customized up to 1.0 |
| Giant II 80K | 0.9, customized up to 1.0 |
| Giant II 100K | 0.9, customized up to 1.0 |
| Giant II 120K | 0.9, customized up to 1.0 |
| Giant II 160K | 0.9, customized up to 1.0 |
Nominal Output Voltage
| Giant II 10K | 380VAC/400VAC/415VAC |
|---|---|
| Giant II 15K | 380VAC/400VAC/415VAC |
| Giant II 20K | 380VAC/400VAC/415VAC |
| Giant II 30K | 380VAC/400VAC/415VAC |
| Giant II 40K | 380VAC/400VAC/415VAC |
| Giant II 60K | 380VAC/400VAC/415VAC |
| Giant II 80K | 380VAC/400VAC/415VAC |
| Giant II 100K | 380VAC/400VAC/415VAC |
| Giant II 120K | 380VAC/400VAC/415VAC |
| Giant II 160K | 380VAC/400VAC/415VAC |
Output Voltage Regulation
| Giant II 10K | ±1% |
|---|---|
| Giant II 15K | ±1% |
| Giant II 20K | ±1% |
| Giant II 30K | ±1% |
| Giant II 40K | ±1% |
| Giant II 60K | ±1% |
| Giant II 80K | ±1% |
| Giant II 100K | ±1% |
| Giant II 120K | ±1% |
| Giant II 160K | ±1% |
BYPASS
Input Voltage Range
| Giant II 10K | 285VAC ~ 475VAC |
|---|---|
| Giant II 15K | 285VAC ~ 475VAC |
| Giant II 20K | 285VAC ~ 475VAC |
| Giant II 30K | 285VAC ~ 475VAC |
| Giant II 40K | 285VAC ~ 475VAC |
| Giant II 60K | 285VAC ~ 475VAC |
| Giant II 80K | 285VAC ~ 475VAC |
| Giant II 100K | 285VAC ~ 475VAC |
| Giant II 120K | 285VAC ~ 475VAC |
| Giant II 160K | 285VAC ~ 475VAC |
Nominal Voltage
| Giant II 10K | 380VAC/400VAC/415VAC |
|---|---|
| Giant II 15K | 380VAC/400VAC/415VAC |
| Giant II 20K | 380VAC/400VAC/415VAC |
| Giant II 30K | 380VAC/400VAC/415VAC |
| Giant II 40K | 380VAC/400VAC/415VAC |
| Giant II 60K | 380VAC/400VAC/415VAC |
| Giant II 80K | 380VAC/400VAC/415VAC |
| Giant II 100K | 380VAC/400VAC/415VAC |
| Giant II 120K | 380VAC/400VAC/415VAC |
| Giant II 160K | 380VAC/400VAC/415VAC |
BATTERY
Battery Voltage
| Giant II 10K | 384 VDC (Adjustable) |
|---|---|
| Giant II 15K | 384 VDC (Adjustable) |
| Giant II 20K | 384 VDC (Adjustable) |
| Giant II 30K | 384 VDC (Adjustable) |
| Giant II 40K | 384 VDC (Adjustable) |
| Giant II 60K | 384 VDC (Adjustable) |
| Giant II 80K | 384 VDC (Adjustable) |
| Giant II 100K | 384 VDC (Adjustable) |
| Giant II 120K | 384 VDC (Adjustable) |
| Giant II 160K | 384 VDC (Adjustable) |
Cold Start
| Giant II 10K | Yes |
|---|---|
| Giant II 15K | Yes |
| Giant II 20K | Yes |
| Giant II 30K | Yes |
| Giant II 40K | Yes |
| Giant II 60K | Yes |
| Giant II 80K | Yes |
| Giant II 100K | Yes |
| Giant II 120K | Yes |
| Giant II 160K | Yes |
ENVIRONMENT
Altitude
| Giant II 10K | 1000m |
|---|---|
| Giant II 15K | 1000m |
| Giant II 20K | 1000m |
| Giant II 30K | 1000m |
| Giant II 40K | 1000m |
| Giant II 60K | 1000m |
| Giant II 80K | 1000m |
| Giant II 100K | 1000m |
| Giant II 120K | 1000m |
| Giant II 160K | 1000m |
Operating Temperature
| Giant II 10K | 0~ 50°C |
|---|---|
| Giant II 15K | 0~ 50°C |
| Giant II 20K | 0~ 50°C |
| Giant II 30K | 0~ 50°C |
| Giant II 40K | 0~ 50°C |
| Giant II 60K | 0~ 50°C |
| Giant II 80K | 0~ 50°C |
| Giant II 100K | 0~ 50°C |
| Giant II 120K | 0~ 50°C |
| Giant II 160K | 0~ 50°C |
Humidity
| Giant II 10K | 0~95% (non-condensing) |
|---|---|
| Giant II 15K | 0~95% (non-condensing) |
| Giant II 20K | 0~95% (non-condensing) |
| Giant II 30K | 0~95% (non-condensing) |
| Giant II 40K | 0~95% (non-condensing) |
| Giant II 60K | 0~95% (non-condensing) |
| Giant II 80K | 0~95% (non-condensing) |
| Giant II 100K | 0~95% (non-condensing) |
| Giant II 120K | 0~95% (non-condensing) |
| Giant II 160K | 0~95% (non-condensing) |
Storage Temperature
| Giant II 10K | -25°C ~ 55°C |
|---|---|
| Giant II 15K | -25°C ~ 55°C |
| Giant II 20K | -25°C ~ 55°C |
| Giant II 30K | -25°C ~ 55°C |
| Giant II 40K | -25°C ~ 55°C |
| Giant II 60K | -25°C ~ 55°C |
| Giant II 80K | -25°C ~ 55°C |
| Giant II 100K | -25°C ~ 55°C |
| Giant II 120K | -25°C ~ 55°C |
| Giant II 160K | -25°C ~ 55°C |
PHYSICAL
Net Weight (Kgs)
| Giant II 10K | 120 |
|---|---|
| Giant II 15K | 145 |
| Giant II 20K | 193 |
| Giant II 30K | 278 |
| Giant II 40K | 365 |
| Giant II 60K | 471 |
| Giant II 80K | 573 |
| Giant II 100K | 650 |
| Giant II 120K | 735 |
| Giant II 160K | 790 |
IP Protection
| Giant II 10K | IP31 (default), IP42 (optional) |
|---|---|
| Giant II 15K | IP31 (default), IP42 (optional) |
| Giant II 20K | IP31 (default), IP42 (optional) |
| Giant II 30K | IP31 (default), IP42 (optional) |
| Giant II 40K | IP31 (default), IP42 (optional) |
| Giant II 60K | IP31 (default), IP42 (optional) |
| Giant II 80K | IP31 (default), IP42 (optional) |
| Giant II 100K | IP31 (default), IP42 (optional) |
| Giant II 120K | IP31 (default), IP42 (optional) |
| Giant II 160K | IP31 (default), IP42 (optional) |
Dimensions, D x W x H(mm)
| Giant II 10K | 656 x 405 x 817 |
|---|---|
| Giant II 15K | 656 x 405 x 817 |
| Giant II 20K | 656 x 405 x 941 |
| Giant II 30K | 821 x 432 x 1159 |
| Giant II 40K | 821 x 432 x 1159 |
| Giant II 60K | 800 x 1200 x 1800 |
| Giant II 80K | 800 x 1200 x 1800 |
| Giant II 100K | 975 x 635 x 1326 |
| Giant II 120K | 1051x705x1646 |
| Giant II 160K | 1051x705x1646 |
MANAGEMENT
Optional SNMP
| Giant II 10K | Power management from SNMP manager and web browser |
|---|---|
| Giant II 15K | Power management from SNMP manager and web browser |
| Giant II 20K | Power management from SNMP manager and web browser |
| Giant II 30K | Power management from SNMP manager and web browser |
| Giant II 40K | Power management from SNMP manager and web browser |
| Giant II 60K | Power management from SNMP manager and web browser |
| Giant II 80K | Power management from SNMP manager and web browser |
| Giant II 100K | Power management from SNMP manager and web browser |
| Giant II 120K | Power management from SNMP manager and web browser |
| Giant II 160K | Power management from SNMP manager and web browser |
Modbus RS-232 / RS485
| Giant II 10K | Supports Windows® family, Linux and MAC |
|---|---|
| Giant II 15K | Supports Windows® family, Linux and MAC |
| Giant II 20K | Supports Windows® family, Linux and MAC |
| Giant II 30K | Supports Windows® family, Linux and MAC |
| Giant II 40K | Supports Windows® family, Linux and MAC |
| Giant II 60K | Supports Windows® family, Linux and MAC |
| Giant II 80K | Supports Windows® family, Linux and MAC |
| Giant II 100K | Supports Windows® family, Linux and MAC |
| Giant II 120K | Supports Windows® family, Linux and MAC |
| Giant II 160K | Supports Windows® family, Linux and MAC |
Dry Contacts
| Giant II 10K | 5 outputs and 4 inputs |
|---|---|
| Giant II 15K | 5 outputs and 4 inputs |
| Giant II 20K | 5 outputs and 4 inputs |
| Giant II 30K | 5 outputs and 4 inputs |
| Giant II 40K | 5 outputs and 4 inputs |
| Giant II 60K | 5 outputs and 4 inputs |
| Giant II 80K | 5 outputs and 4 inputs |
| Giant II 100K | 5 outputs and 4 inputs |
| Giant II 120K | 5 outputs and 4 inputs |
| Giant II 160K | 5 outputs and 4 inputs |
STANDARD
Safety
| Giant II 10K | IEC62040-1-2017 |
|---|---|
| Giant II 15K | IEC62040-1-2017 |
| Giant II 20K | IEC62040-1-2017 |
| Giant II 30K | IEC62040-1-2017 |
| Giant II 40K | IEC62040-1-2017 |
| Giant II 60K | IEC62040-1-2017 |
| Giant II 80K | IEC62040-1-2017 |
| Giant II 100K | IEC62040-1-2017 |
| Giant II 120K | IEC62040-1-2017 |
| Giant II 160K | IEC62040-1-2017 |
| Brochure | Giant_II_33 | |
| Manual | Giant ll 33 Manual |