Giant Elite 3P/1P 6K/7.5K/10KVA
Embedded with isolation transformer
Embedded with isolation transformer, Giant series will eliminate common mode noise and the need to install expensive dedicated circuits. It provides reliable galvanically isolated power to critical equipment.


Main Features
- Galvanic isolation design to withstand all kinds of loads
- Output power factor 0.8
- Fully coating PCBAs to withstand harsh environment
- Unique ventilation design for effective heat dissipation
- Wide input voltage and frequency range to withstand robust environment
- High short-circuit and overload capabilities
- Built-in maintenance bypass switch
MODEL | Giant Elite 31-6K(L) | Giant Elite 31-7.5K(L) | Giant Elite 31-10K(L) | |
CAPACITY | 6 KVA / 4.8 KW | 7.5 KVA / 6 KW | 10 KVA / 8 KW | |
PHASE | 3-phase in / 1-phase out | 3-phase in / 1-phase out | 3-phase in / 1-phase out | |
INPUT | ||||
Nominal Voltage | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) | |
Acceptable Voltage Range | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries | |
Frequency | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system | |
OUTPUT | ||||
Voltage Regulation | ± 1% | ± 1% | ± 1% | |
Output Voltage | 208VAC/220VAC/230VAC (Selectable) | 208VAC/220VAC/230VAC (Selectable) | 208VAC/220VAC/230VAC (Selectable) | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
Transfer Time | AC to DC | Zero | Zero | Zero |
Transfer Time | Inverter to Bypass | Zero | Zero | Zero |
Transfer Time | Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave |
Efficiency | Battery Mode | 92% | 92% | 92% |
Efficiency | Line Mode | 83% | 83% | 83% |
Frequency Range | 45Hz~55 Hz or 56 Hz~64 Hz | 45Hz~55 Hz or 56 Hz~64 Hz | 45Hz~55 Hz or 56 Hz~64 Hz | |
Current Crest Ratio | 3:1 | 3:1 | 3:1 | |
Harmonic Distortion | <3% THD (Linear Load); <5% THD (Non-linear Load) | <3% THD (Linear Load); <5% THD (Non-linear Load) | <3% THD (Linear Load); <5% THD (Non-linear Load) | |
BATTERY | ||||
Long-run Model | Battery Numbers | 16pcs, 18 pcs | 16pcs, 18 pcs | 16pcs, 18 pcs |
Long-run Model | Battery Type | Depending on the applications | Depending on the applications | Depending on the applications |
Long-run Model | Charging Current (max.) | Default: 8A, 2A/4A/8A(adjustable) | Default: 8A, 2A/4A/8A(adjustable) | Default: 8A, 2A/4A/8A(adjustable) |
Long-run Model | Charging Voltage | 218.4 V ± 1%, 245.7 V ± 1% | 218.4 V ± 1%, 245.7 V ± 1% | 218.4 V ± 1%, 245.7 V ± 1% |
Standard Model | Battery Numbers | 16pcs | 16pcs | 16pcs |
Standard Model | Battery Type | 12V / 9Ah | 12V / 9Ah | 12V / 9Ah |
Standard Model | Charging Current (max.) | 2A | 2A | 2A |
Standard Model | Charging Voltage | 218.4 V ± 1% | 218.4 V ± 1% | 218.4 V ± 1% |
Standard Model | Recharge Time | 6 hours recover to 90% capacity | 6 hours recover to 90% capacity | 6 hours recover to 90% capacity |
INDICATORS | ||||
LCD | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code | |
ALARM | ||||
Battery Mode | Sounding every 4 seconds | Sounding every 4 seconds | Sounding every 4 seconds | |
Low Battery | Sounding every second | Sounding every second | Sounding every second | |
Overload | Sounding twice every second | Sounding twice every second | Sounding twice every second | |
Fault | Continuously sounding | Continuously sounding | Continuously sounding | |
ENVIRONMENT | ||||
Operating Temperature | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) | |
Operating Humidity | <95% and non-condersing | <95% and non-condersing | <95% and non-condersing | |
Noise Level | Less than 60dB @ 1 Meter | Less than 60dB @ 1 Meter | Less than 60dB @ 1 Meter | |
PHYSICAL | ||||
Standard Model | Dimensions, D x W x H(mm) | 592 x 300 x 826, 592 x 360 x 826 | 592 x 300 x 826, 592 x 360 x 826 | 592 x 300 x 826, 592 x 360 x 826 |
Standard Model | Net Weight (Kgs) | 129, 137 | 152, 160 | 160, 168 |
Long-run Model | Dimensions, D x W x H(mm) | 592 x 300 x 826 | 592 x 300 x 826 | 592 x 300 x 826 |
Long-run Model | Net Weight (Kgs) | 84 | 107 | 115 |
MANAGEMENT | ||||
Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
Modbus RS-232 / RS485 | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC |
General
CAPACITY
Giant Elite 31-6K(L) | 6 KVA / 4.8 KW |
---|---|
Giant Elite 31-7.5K(L) | 7.5 KVA / 6 KW |
Giant Elite 31-10K(L) | 10 KVA / 8 KW |
PHASE
Giant Elite 31-6K(L) | 3-phase in / 1-phase out |
---|---|
Giant Elite 31-7.5K(L) | 3-phase in / 1-phase out |
Giant Elite 31-10K(L) | 3-phase in / 1-phase out |
INPUT
Nominal Voltage
Giant Elite 31-6K(L) | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) |
---|---|
Giant Elite 31-7.5K(L) | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) |
Giant Elite 31-10K(L) | 3 x 360VAC/380VAC/400VAC (3Ph + N + G) |
Acceptable Voltage Range
Giant Elite 31-6K(L) | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries |
---|---|
Giant Elite 31-7.5K(L) | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries |
Giant Elite 31-10K(L) | 286VAC~493VAC @ 16 pcs of batteries; 320VAC~493VAC @ 18 pcs of batteries |
Frequency
Giant Elite 31-6K(L) | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system |
---|---|
Giant Elite 31-7.5K(L) | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system |
Giant Elite 31-10K(L) | 40Hz~55 Hz @ 50Hz system; 56 Hz~64Hz @ 60Hz system |
OUTPUT
Voltage Regulation
Giant Elite 31-6K(L) | ± 1% |
---|---|
Giant Elite 31-7.5K(L) | ± 1% |
Giant Elite 31-10K(L) | ± 1% |
Output Voltage
Giant Elite 31-6K(L) | 208VAC/220VAC/230VAC (Selectable) |
---|---|
Giant Elite 31-7.5K(L) | 208VAC/220VAC/230VAC (Selectable) |
Giant Elite 31-10K(L) | 208VAC/220VAC/230VAC (Selectable) |
Frequency Range (Batt. Mode)
Giant Elite 31-6K(L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
---|---|
Giant Elite 31-7.5K(L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Giant Elite 31-10K(L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Transfer Time AC to DC
Giant Elite 31-6K(L) | Zero |
---|---|
Giant Elite 31-7.5K(L) | Zero |
Giant Elite 31-10K(L) | Zero |
Transfer Time Inverter to Bypass
Giant Elite 31-6K(L) | Zero |
---|---|
Giant Elite 31-7.5K(L) | Zero |
Giant Elite 31-10K(L) | Zero |
Transfer Time Waveform (Batt. Mode)
Giant Elite 31-6K(L) | Pure Sine Wave |
---|---|
Giant Elite 31-7.5K(L) | Pure Sine Wave |
Giant Elite 31-10K(L) | Pure Sine Wave |
Efficiency Battery Mode
Giant Elite 31-6K(L) | 92% |
---|---|
Giant Elite 31-7.5K(L) | 92% |
Giant Elite 31-10K(L) | 92% |
Efficiency Line Mode
Giant Elite 31-6K(L) | 83% |
---|---|
Giant Elite 31-7.5K(L) | 83% |
Giant Elite 31-10K(L) | 83% |
Frequency Range
Giant Elite 31-6K(L) | 45Hz~55 Hz or 56 Hz~64 Hz |
---|---|
Giant Elite 31-7.5K(L) | 45Hz~55 Hz or 56 Hz~64 Hz |
Giant Elite 31-10K(L) | 45Hz~55 Hz or 56 Hz~64 Hz |
Current Crest Ratio
Giant Elite 31-6K(L) | 3:1 |
---|---|
Giant Elite 31-7.5K(L) | 3:1 |
Giant Elite 31-10K(L) | 3:1 |
Harmonic Distortion
Giant Elite 31-6K(L) | <3% THD (Linear Load); <5% THD (Non-linear Load) |
---|---|
Giant Elite 31-7.5K(L) | <3% THD (Linear Load); <5% THD (Non-linear Load) |
Giant Elite 31-10K(L) | <3% THD (Linear Load); <5% THD (Non-linear Load) |
BATTERY
Long-run Model Battery Numbers
Giant Elite 31-6K(L) | 16pcs, 18 pcs |
---|---|
Giant Elite 31-7.5K(L) | 16pcs, 18 pcs |
Giant Elite 31-10K(L) | 16pcs, 18 pcs |
Long-run Model Battery Type
Giant Elite 31-6K(L) | Depending on the applications |
---|---|
Giant Elite 31-7.5K(L) | Depending on the applications |
Giant Elite 31-10K(L) | Depending on the applications |
Long-run Model Charging Current (max.)
Giant Elite 31-6K(L) | Default: 8A, 2A/4A/8A(adjustable) |
---|---|
Giant Elite 31-7.5K(L) | Default: 8A, 2A/4A/8A(adjustable) |
Giant Elite 31-10K(L) | Default: 8A, 2A/4A/8A(adjustable) |
Long-run Model Charging Voltage
Giant Elite 31-6K(L) | 218.4 V ± 1%, 245.7 V ± 1% |
---|---|
Giant Elite 31-7.5K(L) | 218.4 V ± 1%, 245.7 V ± 1% |
Giant Elite 31-10K(L) | 218.4 V ± 1%, 245.7 V ± 1% |
Standard Model Battery Numbers
Giant Elite 31-6K(L) | 16pcs |
---|---|
Giant Elite 31-7.5K(L) | 16pcs |
Giant Elite 31-10K(L) | 16pcs |
Standard Model Battery Type
Giant Elite 31-6K(L) | 12V / 9Ah |
---|---|
Giant Elite 31-7.5K(L) | 12V / 9Ah |
Giant Elite 31-10K(L) | 12V / 9Ah |
Standard Model Charging Current (max.)
Giant Elite 31-6K(L) | 2A |
---|---|
Giant Elite 31-7.5K(L) | 2A |
Giant Elite 31-10K(L) | 2A |
Standard Model Charging Voltage
Giant Elite 31-6K(L) | 218.4 V ± 1% |
---|---|
Giant Elite 31-7.5K(L) | 218.4 V ± 1% |
Giant Elite 31-10K(L) | 218.4 V ± 1% |
Standard Model Recharge Time
Giant Elite 31-6K(L) | 6 hours recover to 90% capacity |
---|---|
Giant Elite 31-7.5K(L) | 6 hours recover to 90% capacity |
Giant Elite 31-10K(L) | 6 hours recover to 90% capacity |
INDICATORS
LCD
Giant Elite 31-6K(L) | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code |
---|---|
Giant Elite 31-7.5K(L) | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code |
Giant Elite 31-10K(L) | UPS status, load level, battery level, input/output voltage and frequency, fault code/warning code |
ALARM
Battery Mode
Giant Elite 31-6K(L) | Sounding every 4 seconds |
---|---|
Giant Elite 31-7.5K(L) | Sounding every 4 seconds |
Giant Elite 31-10K(L) | Sounding every 4 seconds |
Low Battery
Giant Elite 31-6K(L) | Sounding every second |
---|---|
Giant Elite 31-7.5K(L) | Sounding every second |
Giant Elite 31-10K(L) | Sounding every second |
Overload
Giant Elite 31-6K(L) | Sounding twice every second |
---|---|
Giant Elite 31-7.5K(L) | Sounding twice every second |
Giant Elite 31-10K(L) | Sounding twice every second |
Fault
Giant Elite 31-6K(L) | Continuously sounding |
---|---|
Giant Elite 31-7.5K(L) | Continuously sounding |
Giant Elite 31-10K(L) | Continuously sounding |
ENVIRONMENT
Operating Temperature
Giant Elite 31-6K(L) | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) |
---|---|
Giant Elite 31-7.5K(L) | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) |
Giant Elite 31-10K(L) | 0~50°C (battery life cycle will be shorten when temperature is above 25°C) |
Operating Humidity
Giant Elite 31-6K(L) | <95% and non-condersing |
---|---|
Giant Elite 31-7.5K(L) | <95% and non-condersing |
Giant Elite 31-10K(L) | <95% and non-condersing |
Noise Level
Giant Elite 31-6K(L) | Less than 60dB @ 1 Meter |
---|---|
Giant Elite 31-7.5K(L) | Less than 60dB @ 1 Meter |
Giant Elite 31-10K(L) | Less than 60dB @ 1 Meter |
PHYSICAL
Standard Model Dimensions, D x W x H(mm)
Giant Elite 31-6K(L) | 592 x 300 x 826, 592 x 360 x 826 |
---|---|
Giant Elite 31-7.5K(L) | 592 x 300 x 826, 592 x 360 x 826 |
Giant Elite 31-10K(L) | 592 x 300 x 826, 592 x 360 x 826 |
Standard Model Net Weight (Kgs)
Giant Elite 31-6K(L) | 129, 137 |
---|---|
Giant Elite 31-7.5K(L) | 152, 160 |
Giant Elite 31-10K(L) | 160, 168 |
Long-run Model Dimensions, D x W x H(mm)
Giant Elite 31-6K(L) | 592 x 300 x 826 |
---|---|
Giant Elite 31-7.5K(L) | 592 x 300 x 826 |
Giant Elite 31-10K(L) | 592 x 300 x 826 |
Long-run Model Net Weight (Kgs)
Giant Elite 31-6K(L) | 84 |
---|---|
Giant Elite 31-7.5K(L) | 107 |
Giant Elite 31-10K(L) | 115 |
MANAGEMENT
Optional SNMP
Giant Elite 31-6K(L) | Power management from SNMP manager and web browser |
---|---|
Giant Elite 31-7.5K(L) | Power management from SNMP manager and web browser |
Giant Elite 31-10K(L) | Power management from SNMP manager and web browser |
Modbus RS-232 / RS485
Giant Elite 31-6K(L) | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC |
---|---|
Giant Elite 31-7.5K(L) | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC |
Giant Elite 31-10K(L) | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC |
![]() |
Brochure | Giant Elite 3P/1P 6K/7.5K/10KVA |
![]() |
Manual | Giant Elite 3P/1P 6K/7.5K/10KVA |
Three phase - Online UPS Giant Elite 3P/1P 6K/7.5K/10KVA Embedded with isolation transformer