14
Galleon One 1KVA-10KVA
Premium featured Online UPS
With true double-conversion design, Galleon series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. Its perfect protection for your precious servers and workstations. For Galleon One with cTUVus or isolation transformer specs, please check our sales directly.
Main Features
- True double-conversion
- Output power factor 1
- Built-in 2.8 touch LCD for comprehensive UPS status
- Output voltage regulation 1%
- 50Hz/60Hz frequency converter mode
- Programmable power management outlets
- Hot swappable battery design
- ECO mode energy saving
- Provides over voltage cut-off protection and surge immunity by MOV for full time equipment protection
- High power factor charger up to 8A/12A capacity with very low ripple current when charging battery
- Low input THDi to reduce power system pollution
- Adjustable charging current via LCD panel
- Optional HID Power Device USB Port
MODEL | Galleon One 1K | Galleon One 1.5K | Galleon One 2K | Galleon One 3K | Galleon One 6K(L) | Galleon One 10K (L) | |
PHASE | Single phase with ground | Single phase with ground | Single phase with ground | Single phase with ground | 1 phase in / 1 phase out | 1 phase in / 1 phase out | |
CAPACITY* | 1000 VA / 1000 W | 1500 VA / 1500 W | 2000 VA / 2000 W | 3000 VA / 3000 W | 6000 VA / 6000 W | 10000 VA / 10000 W | |
INPUT | |||||||
Voltage Range | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load | 110-300 VAC ± 3 % at 50% load; 176~300 VAC ± 3 % at 100% load | 110-300 VAC ± 3 % at 50% load; 176~300 VAC ± 3 % at 100% load | |
Nominal Voltage | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC | 208/220/230/240 VAC | 208/220/230/240 VAC | |
Frequency Range | 40Hz~70Hz | 40Hz~70Hz | 40Hz~70Hz | 40Hz~70Hz | 46~54 Hz or 56~64 Hz | 46~54 Hz or 56~64 Hz | |
Power Factor | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ full load | ≧ 0.99 @ full load | |
Harmonic Distortion (THDi) | ≦ 5% | ≦ 5% | ≦ 5% | ≦ 5% | < 4% @100% Load, < 6% @50% Load | < 4% @100% Load, < 6% @50% Load | |
OUTPUT | |||||||
Output Voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 208/220/230/240 VAC | 208/220/230/240 VAC | |
AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% | ± 1% | ± 1% | ± 1% | ± 1% | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
Transfer Time | AC to DC | Zero | Zero | Zero | Zero | Zero | Zero |
Transfer Time | ECO to Battery mode | 8 ms (Typical), 10 ms(max) | 8 ms (Typical), 10 ms(max) | 8 ms (Typical), 10 ms(max) | 8 ms (Typical), 10 ms(max) | ||
Transfer Time | Inverter to Bypass | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) | zero | zero |
Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | |
Current Crest Ratio | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 (max.) | 3:1 (max.) | |
Harmonic Distortion | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | ≦ 1% THD (Linear Load), ≦ 4% THD (Non-linear Load) | ≦ 1% THD (Linear Load), ≦ 4% THD (Non-linear Load) | |
Frequency Range (Synchronized Range) | 47~53 Hz or 57~63Hz | 47~53 Hz or 57~63Hz | 47~53 Hz or 57~63Hz | 47~53 Hz or 57~63Hz | 46~54 Hz or 56~64 Hz | 46~54 Hz or 56~64 Hz | |
Overload | AC Mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | ||||
Overload | Battery Mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||
EFFICIENCY | |||||||
Battery Mode | ≧88% | ≧88% | ≧90% | ≧90% | 91% | 91% | |
ECO Mode | ≧ 96% @ full charged battery | ≧ 96% @ full charged battery | ≧ 96% @ full charged battery | ≧ 96% @ full charged battery | |||
AC Mode | ≧ 89% @ full charged battery | ≧ 89% @ full charged battery | ≧ 91% @ full charged battery | ≧ 91% @ full charged battery | 94% | 94% | |
BATTERY | |||||||
Long-run Model | Battery Type | Depending on applications | Depending on applications | ||||
Long-run Model | Charging Current (max.) | 4.0 A | 4.0 A | ||||
Long-run Model | Charging Voltage | (13.65VDC x battery number) ± 1% | (13.65VDC x battery number) ± 1% | ||||
Long-run Model | Numbers | 16-20** | 16-20** | ||||
Standard Model | Battery Type | 12 V / 9 AH, 12 V / 7 AH | 12 V / 9 AH | 12 V / 9 AH, 12 V / 7 AH | 12 V / 9 AH, 12 V / 7 AH | 12 V / 7 AH | 12 V / 9 AH |
Standard Model | Charging Current | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable | Default: 2A, Max: 8A adjustable | 1.0 A | 1.0 A |
Standard Model | Charging Voltage | 27.4 VDC ± 1%,41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ± 1%, 82.1 VDC ± 1% | 82.1 VDC ± 1% ,109.6 VDC ± 1% | 218.4 VDC ± 1% | 218.4 VDC ± 1% |
Standard Model | Numbers | 2,3 | 3 | 4, 6 | 6, 8 | 16 | 16 |
Standard Model | Typical Recharge Time | 3 hours recover to 95% capacity for internal battery@ 2A charging current | 3 hours recover to 95% capacity for internal battery@ 2A charging current | 3 hours recover to 95% capacity for internal battery@ 2A charging current | 3 hours recover to 95% capacity for internal battery@ 2A charging current | 9 hours recover to 90% capacity | 9 hours recover to 90% capacity |
INDICATORS | |||||||
LCD Panel | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
ALARM | |||||||
Battery Mode | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 4 seconds | Sounding every 4 seconds | |
Low Battery | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | |
Overload | Sounding every second | Sounding every second | Sounding every second | Sounding every second | Sounding twice every second | Sounding twice every second | |
Fault | Continuously sounding | Continuously sounding | Continuously sounding | Continuously sounding | Continuously sounding | Continuously sounding | |
ENVIRONMENT | |||||||
Operating Humidity | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 50dB @ 1 Meter with Fan speed control | Less than 50dB @ 1 Meter with Fan speed control | Less than 50dB @ 1 Meter with Fan speed control | Less than 50dB @ 1 Meter with Fan speed control | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | |
PHYSICAL | |||||||
Standard Model | Dimension, D X W X H (mm) | 397 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 | 421 x 190 x 318 | 369 x 190 x 688 | 442 x 190 x 688 |
Standard Model | Net Weight (w/built-in battery) (kgs) | 11.7, 13 | 14.6 | 20.3, 23.2 | 28, 33 | 54 | 66 |
Long-run Model | Dimension, D X W X H (mm) | 397 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 | 421 x 190 x 318 | 369 x 190 x 318 | 442 x 190 x 318 |
Long-run Model | Net Weight (without battery) (kgs) | 6.6 | 7 | 9.9 | 12.3 | 13 | 16 |
MANAGEMENT | |||||||
Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | |
STANDARDS | |||||||
Safety | EMC EN62040-2 C2 for CE models | EMC EN62040-2 C2 for CE models | EMC EN62040-2 C2 for CE models | EMC EN62040-2 C2 for CE models |
General
PHASE
Galleon One 1K | Single phase with ground |
---|---|
Galleon One 1.5K | Single phase with ground |
Galleon One 2K | Single phase with ground |
Galleon One 3K | Single phase with ground |
Galleon One 6K(L) | 1 phase in / 1 phase out |
Galleon One 10K (L) | 1 phase in / 1 phase out |
CAPACITY*
Galleon One 1K | 1000 VA / 1000 W |
---|---|
Galleon One 1.5K | 1500 VA / 1500 W |
Galleon One 2K | 2000 VA / 2000 W |
Galleon One 3K | 3000 VA / 3000 W |
Galleon One 6K(L) | 6000 VA / 6000 W |
Galleon One 10K (L) | 10000 VA / 10000 W |
INPUT
Voltage Range
Galleon One 1K | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load |
---|---|
Galleon One 1.5K | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load |
Galleon One 2K | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load |
Galleon One 3K | 55-150 VAC ± 3 % or 110-300 VAC ± 3 % at 50% load; 80-150 VAC ± 3 % or 160-300 VAC ± 3 % at 100% load |
Galleon One 6K(L) | 110-300 VAC ± 3 % at 50% load; 176~300 VAC ± 3 % at 100% load |
Galleon One 10K (L) | 110-300 VAC ± 3 % at 50% load; 176~300 VAC ± 3 % at 100% load |
Nominal Voltage
Galleon One 1K | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon One 1.5K | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC |
Galleon One 2K | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC |
Galleon One 3K | 100/110/115/120 /127 VAC or 200/208/220/230/240 VAC |
Galleon One 6K(L) | 208/220/230/240 VAC |
Galleon One 10K (L) | 208/220/230/240 VAC |
Frequency Range
Galleon One 1K | 40Hz~70Hz |
---|---|
Galleon One 1.5K | 40Hz~70Hz |
Galleon One 2K | 40Hz~70Hz |
Galleon One 3K | 40Hz~70Hz |
Galleon One 6K(L) | 46~54 Hz or 56~64 Hz |
Galleon One 10K (L) | 46~54 Hz or 56~64 Hz |
Power Factor
Galleon One 1K | ≧ 0.99 @ Nominal Voltage (100% load) |
---|---|
Galleon One 1.5K | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon One 2K | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon One 3K | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon One 6K(L) | ≧ 0.99 @ full load |
Galleon One 10K (L) | ≧ 0.99 @ full load |
Harmonic Distortion (THDi)
Galleon One 1K | ≦ 5% |
---|---|
Galleon One 1.5K | ≦ 5% |
Galleon One 2K | ≦ 5% |
Galleon One 3K | ≦ 5% |
Galleon One 6K(L) | < 4% @100% Load, < 6% @50% Load |
Galleon One 10K (L) | < 4% @100% Load, < 6% @50% Load |
OUTPUT
Output Voltage
Galleon One 1K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon One 1.5K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon One 2K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon One 3K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon One 6K(L) | 208/220/230/240 VAC |
Galleon One 10K (L) | 208/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode)
Galleon One 1K | ± 1% |
---|---|
Galleon One 1.5K | ± 1% |
Galleon One 2K | ± 1% |
Galleon One 3K | ± 1% |
Galleon One 6K(L) | ± 1% |
Galleon One 10K (L) | ± 1% |
Frequency Range (Batt. Mode)
Galleon One 1K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
---|---|
Galleon One 1.5K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon One 2K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon One 3K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon One 6K(L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon One 10K (L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Transfer Time AC to DC
Galleon One 1K | Zero |
---|---|
Galleon One 1.5K | Zero |
Galleon One 2K | Zero |
Galleon One 3K | Zero |
Galleon One 6K(L) | Zero |
Galleon One 10K (L) | Zero |
Transfer Time ECO to Battery mode
Galleon One 1K | 8 ms (Typical), 10 ms(max) |
---|---|
Galleon One 1.5K | 8 ms (Typical), 10 ms(max) |
Galleon One 2K | 8 ms (Typical), 10 ms(max) |
Galleon One 3K | 8 ms (Typical), 10 ms(max) |
Galleon One 6K(L) | |
Galleon One 10K (L) |
Transfer Time Inverter to Bypass
Galleon One 1K | 4 ms (Typical) |
---|---|
Galleon One 1.5K | 4 ms (Typical) |
Galleon One 2K | 4 ms (Typical) |
Galleon One 3K | 4 ms (Typical) |
Galleon One 6K(L) | zero |
Galleon One 10K (L) | zero |
Waveform (Batt. Mode)
Galleon One 1K | Pure Sine Wave |
---|---|
Galleon One 1.5K | Pure Sine Wave |
Galleon One 2K | Pure Sine Wave |
Galleon One 3K | Pure Sine Wave |
Galleon One 6K(L) | Pure Sine Wave |
Galleon One 10K (L) | Pure Sine Wave |
Current Crest Ratio
Galleon One 1K | 3:1 |
---|---|
Galleon One 1.5K | 3:1 |
Galleon One 2K | 3:1 |
Galleon One 3K | 3:1 |
Galleon One 6K(L) | 3:1 (max.) |
Galleon One 10K (L) | 3:1 (max.) |
Harmonic Distortion
Galleon One 1K | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) |
---|---|
Galleon One 1.5K | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) |
Galleon One 2K | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) |
Galleon One 3K | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) |
Galleon One 6K(L) | ≦ 1% THD (Linear Load), ≦ 4% THD (Non-linear Load) |
Galleon One 10K (L) | ≦ 1% THD (Linear Load), ≦ 4% THD (Non-linear Load) |
Frequency Range (Synchronized Range)
Galleon One 1K | 47~53 Hz or 57~63Hz |
---|---|
Galleon One 1.5K | 47~53 Hz or 57~63Hz |
Galleon One 2K | 47~53 Hz or 57~63Hz |
Galleon One 3K | 47~53 Hz or 57~63Hz |
Galleon One 6K(L) | 46~54 Hz or 56~64 Hz |
Galleon One 10K (L) | 46~54 Hz or 56~64 Hz |
Overload AC Mode
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec |
Galleon One 10K (L) | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec |
Overload Battery Mode
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec |
Galleon One 10K (L) | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec |
EFFICIENCY
Battery Mode
Galleon One 1K | ≧88% |
---|---|
Galleon One 1.5K | ≧88% |
Galleon One 2K | ≧90% |
Galleon One 3K | ≧90% |
Galleon One 6K(L) | 91% |
Galleon One 10K (L) | 91% |
ECO Mode
Galleon One 1K | ≧ 96% @ full charged battery |
---|---|
Galleon One 1.5K | ≧ 96% @ full charged battery |
Galleon One 2K | ≧ 96% @ full charged battery |
Galleon One 3K | ≧ 96% @ full charged battery |
Galleon One 6K(L) | |
Galleon One 10K (L) |
AC Mode
Galleon One 1K | ≧ 89% @ full charged battery |
---|---|
Galleon One 1.5K | ≧ 89% @ full charged battery |
Galleon One 2K | ≧ 91% @ full charged battery |
Galleon One 3K | ≧ 91% @ full charged battery |
Galleon One 6K(L) | 94% |
Galleon One 10K (L) | 94% |
BATTERY
Long-run Model Battery Type
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | Depending on applications |
Galleon One 10K (L) | Depending on applications |
Long-run Model Charging Current (max.)
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | 4.0 A |
Galleon One 10K (L) | 4.0 A |
Long-run Model Charging Voltage
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | (13.65VDC x battery number) ± 1% |
Galleon One 10K (L) | (13.65VDC x battery number) ± 1% |
Long-run Model Numbers
Galleon One 1K | |
---|---|
Galleon One 1.5K | |
Galleon One 2K | |
Galleon One 3K | |
Galleon One 6K(L) | 16-20** |
Galleon One 10K (L) | 16-20** |
Standard Model Battery Type
Galleon One 1K | 12 V / 9 AH, 12 V / 7 AH |
---|---|
Galleon One 1.5K | 12 V / 9 AH |
Galleon One 2K | 12 V / 9 AH, 12 V / 7 AH |
Galleon One 3K | 12 V / 9 AH, 12 V / 7 AH |
Galleon One 6K(L) | 12 V / 7 AH |
Galleon One 10K (L) | 12 V / 9 AH |
Standard Model Charging Current
Galleon One 1K | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable |
---|---|
Galleon One 1.5K | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable |
Galleon One 2K | 100/110/115/120 /127 VAC models: default 2A, max. 8A adjustable; 200/208/220/230/240 VAC models: default 2A, max. 12A adjustable |
Galleon One 3K | Default: 2A, Max: 8A adjustable |
Galleon One 6K(L) | 1.0 A |
Galleon One 10K (L) | 1.0 A |
Standard Model Charging Voltage
Galleon One 1K | 27.4 VDC ± 1%,41.1 VDC ± 1% |
---|---|
Galleon One 1.5K | 41.1 VDC ± 1% |
Galleon One 2K | 54.8 VDC ± 1%, 82.1 VDC ± 1% |
Galleon One 3K | 82.1 VDC ± 1% ,109.6 VDC ± 1% |
Galleon One 6K(L) | 218.4 VDC ± 1% |
Galleon One 10K (L) | 218.4 VDC ± 1% |
Standard Model Numbers
Galleon One 1K | 2,3 |
---|---|
Galleon One 1.5K | 3 |
Galleon One 2K | 4, 6 |
Galleon One 3K | 6, 8 |
Galleon One 6K(L) | 16 |
Galleon One 10K (L) | 16 |
Standard Model Typical Recharge Time
Galleon One 1K | 3 hours recover to 95% capacity for internal battery@ 2A charging current |
---|---|
Galleon One 1.5K | 3 hours recover to 95% capacity for internal battery@ 2A charging current |
Galleon One 2K | 3 hours recover to 95% capacity for internal battery@ 2A charging current |
Galleon One 3K | 3 hours recover to 95% capacity for internal battery@ 2A charging current |
Galleon One 6K(L) | 9 hours recover to 90% capacity |
Galleon One 10K (L) | 9 hours recover to 90% capacity |
INDICATORS
LCD Panel
Galleon One 1K | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions |
---|---|
Galleon One 1.5K | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions |
Galleon One 2K | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions |
Galleon One 3K | Load level, Battery level, AC mode, Battery Mode, Bypass mode, and Fault conditions |
Galleon One 6K(L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
Galleon One 10K (L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
ALARM
Battery Mode
Galleon One 1K | Sounding every 5 seconds |
---|---|
Galleon One 1.5K | Sounding every 5 seconds |
Galleon One 2K | Sounding every 5 seconds |
Galleon One 3K | Sounding every 5 seconds |
Galleon One 6K(L) | Sounding every 4 seconds |
Galleon One 10K (L) | Sounding every 4 seconds |
Low Battery
Galleon One 1K | Sounding every 2 seconds |
---|---|
Galleon One 1.5K | Sounding every 2 seconds |
Galleon One 2K | Sounding every 2 seconds |
Galleon One 3K | Sounding every 2 seconds |
Galleon One 6K(L) | Sounding every 2 seconds |
Galleon One 10K (L) | Sounding every 2 seconds |
Overload
Galleon One 1K | Sounding every second |
---|---|
Galleon One 1.5K | Sounding every second |
Galleon One 2K | Sounding every second |
Galleon One 3K | Sounding every second |
Galleon One 6K(L) | Sounding twice every second |
Galleon One 10K (L) | Sounding twice every second |
Fault
Galleon One 1K | Continuously sounding |
---|---|
Galleon One 1.5K | Continuously sounding |
Galleon One 2K | Continuously sounding |
Galleon One 3K | Continuously sounding |
Galleon One 6K(L) | Continuously sounding |
Galleon One 10K (L) | Continuously sounding |
ENVIRONMENT
Operating Humidity
Galleon One 1K | 20~95% RH @ 0- 40°C (non-condensing) |
---|---|
Galleon One 1.5K | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon One 2K | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon One 3K | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon One 6K(L) | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon One 10K (L) | 20~95% RH @ 0- 40°C (non-condensing) |
Noise Level
Galleon One 1K | Less than 50dB @ 1 Meter with Fan speed control |
---|---|
Galleon One 1.5K | Less than 50dB @ 1 Meter with Fan speed control |
Galleon One 2K | Less than 50dB @ 1 Meter with Fan speed control |
Galleon One 3K | Less than 50dB @ 1 Meter with Fan speed control |
Galleon One 6K(L) | Less than 55dB @ 1 Meter |
Galleon One 10K (L) | Less than 58dB @ 1 Meter |
PHYSICAL
Standard Model Dimension, D X W X H (mm)
Galleon One 1K | 397 x 145 x 220 |
---|---|
Galleon One 1.5K | 397 x 145 x 220 |
Galleon One 2K | 421 x 190 x 318 |
Galleon One 3K | 421 x 190 x 318 |
Galleon One 6K(L) | 369 x 190 x 688 |
Galleon One 10K (L) | 442 x 190 x 688 |
Standard Model Net Weight (w/built-in battery) (kgs)
Galleon One 1K | 11.7, 13 |
---|---|
Galleon One 1.5K | 14.6 |
Galleon One 2K | 20.3, 23.2 |
Galleon One 3K | 28, 33 |
Galleon One 6K(L) | 54 |
Galleon One 10K (L) | 66 |
Long-run Model Dimension, D X W X H (mm)
Galleon One 1K | 397 x 145 x 220 |
---|---|
Galleon One 1.5K | 397 x 145 x 220 |
Galleon One 2K | 421 x 190 x 318 |
Galleon One 3K | 421 x 190 x 318 |
Galleon One 6K(L) | 369 x 190 x 318 |
Galleon One 10K (L) | 442 x 190 x 318 |
Long-run Model Net Weight (without battery) (kgs)
Galleon One 1K | 6.6 |
---|---|
Galleon One 1.5K | 7 |
Galleon One 2K | 9.9 |
Galleon One 3K | 12.3 |
Galleon One 6K(L) | 13 |
Galleon One 10K (L) | 16 |
MANAGEMENT
Optional SNMP
Galleon One 1K | Power management from SNMP manager and web browser |
---|---|
Galleon One 1.5K | Power management from SNMP manager and web browser |
Galleon One 2K | Power management from SNMP manager and web browser |
Galleon One 3K | Power management from SNMP manager and web browser |
Galleon One 6K(L) | Power management from SNMP manager and web browser |
Galleon One 10K (L) | Power management from SNMP manager and web browser |
Smart RS-232/USB
Galleon One 1K | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
---|---|
Galleon One 1.5K | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon One 2K | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon One 3K | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon One 6K(L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon One 10K (L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
STANDARDS
Safety
Galleon One 1K | EMC EN62040-2 C2 for CE models |
---|---|
Galleon One 1.5K | EMC EN62040-2 C2 for CE models |
Galleon One 2K | EMC EN62040-2 C2 for CE models |
Galleon One 3K | EMC EN62040-2 C2 for CE models |
Galleon One 6K(L) | |
Galleon One 10K (L) |
*Derate capacity to 80% when the output voltage is adjusted to 100VAC.
**The output power factor is based on the input voltage. This figure is based on 127V input voltage.
***cTUVus is available for 1K/ 1.5K/ 2K/ 3K.
**The output power factor is based on the input voltage. This figure is based on 127V input voltage.
***cTUVus is available for 1K/ 1.5K/ 2K/ 3K.
Brochure | GalleonOne-1K-10K | |
Manual | GalleonOne 1-3K | |
Manual | GalleonOne-6-10K |
Single phase - Online UPS Galleon One 1KVA-10KVA Premium featured Online UPS
We have received your membership application and will reply as soon as within 24 hours, before that, please browse our website, thank you.