Galleon III 6KVA/10KVA
Exceptional Energy-Efficient UPS
The Galleon III 6KVA/10KVA utilizes advanced digital control technology, offering rapid self-diagnosis and efficient fault management. Its highly integrated circuitry and optimized design improve resistance to interference, ensuring reliable and stable performance. With a full-load efficiency of up to 95%, it helps significantly lower energy consumption and operational costs. The input power factor is greater than 0.99, and current harmonics are kept below 4%, effectively minimizing energy loss and preventing grid pollution. Its ultra-wide voltage input range allows it to adapt seamlessly to various operating conditions, easily managing challenging power environments and reducing the need to switch to battery power. Furthermore, it supports generator input with an isolation design, delivering a clean, safe, and stable power supply for your equipment.
Main Features
- True double-conversion online UPS
- DSP technology ensures exceptional performance
- Output power factor of 1
- Wide input voltage range (110-300 VAC)
- High efficiency, reaching up to 95%
- Active input power factor correction of 0.99
- Frequency converter mode supporting 50Hz/60Hz
- Adjustable AC charger with up to 6A current
- Compatible with generators
- High overload capacity
- Adjustable number of batteries
- Built-in over-voltage, current, and discharge (OVCD) protection
| MODEL | Galleon III 6K(L*) | Galleon III 10K(L*) | |
| CAPACITY | 6000 VA / 6000 W | 10000 VA / 10000 W | |
| PHASE | 1 phase in / 1 phase out | 1 phase in / 1 phase out | |
| INPUT | |||
| Voltage Range | 110~300VAC ± 3 % at 60% load 176~300VAC ± 3 % at 100% load | 110~300VAC ± 3 % at 60% load 176~300VAC ± 3 % at 100% load | |
| Nominal Voltage | 208/220/230/240 VAC | 208/220/230/240 VAC | |
| Frequency Range | 46~54 Hz or 56~64 Hz 40 ~ 70 Hz (In generator mode) | 46~54 Hz or 56~64 Hz 40 ~ 70 Hz (In generator mode) | |
| Power Factor | ≧ 0.99 @ full load | ≧ 0.99 @ full load | |
| THDi | <4% @100% Load | <4% @100% Load | |
| OUTPUT | |||
| Output Voltage | 208*/220/230/240 VAC | 208*/220/230/240 VAC | |
| AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% | |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
| Transfer Time | AC Mode to Batt. Mode | Zero | Zero |
| Transfer Time | Inverter to Bypass | zero | zero |
| Waveform (Batt. Mode) | Pure Sinewave | Pure Sinewave | |
| Current Crest Ratio | 3:1 (max.) | 3:1 (max.) | |
| Harmonic Distortion | ≦1 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) | ≦1 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) | |
| Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | 46~54 Hz or 56~64 Hz | |
| Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, 125%~150% 1min, >150% transfer to bypass | 100-110% for 60 min, 110-125% for 10 min, 125%~150% 1min, >150% transfer to bypass |
| Overload | Battery Mode | 100-110% for 3 min, 110-130% for 30s ,>130% immediately | 100-110% for 3 min, 110-130% for 30s ,>130% immediately |
| EFFICIENCY | |||
| Battery Mode | 0.92 | 0.92 | |
| AC Mode | 0.95 | 0.95 | |
| BATTERY | |||
| Long-run Model | Battery Type | Depending on applications | Depending on applications |
| Long-run Model | Charging Current (max.) | 2A (Default) ,1A/2A/4A/6A/8A adjustable | 2A (Default) ,1A/2A/4A/6A/8A adjustable |
| Long-run Model | Charging Voltage | (13.65VDC x battery number) ± 1% | (13.65VDC x battery number) ± 1% |
| Long-run Model | Numbers | 16-20** | 16-20** |
| Standard Model | Battery Type | 12 V / 7 AH | 12 V / 9 AH |
| Standard Model | Charging Current (max.) | 1.0 A | 1.0 A |
| Standard Model | Charging Voltage | 218.4 VDC ± 1% | 273 VDC ± 1% |
| Standard Model | Numbers | 16 | 20 |
| Standard Model | Typical Recharge Time | 7 hours recover to 90% capacity | 9 hours recover to 90% capacity |
| ENVIRONMENT | |||
| Noise Level | Less than 55dBA @ 1 Meter | Less than 58dB @ 1 Meter | |
| Operation Humidity | > 95% RH @ 0- 40°C (non-condensing) | > 95% RH @ 0- 40°C (non-condensing) | |
| PHYSICAL | |||
| Standard Model | Dimension, D X W X H (mm) | 369 x 190 x 688 | 442 x 190 x 688 |
| Standard Model | Net Weight (kgs) | 55 | 74 |
| Long-run Model | Dimension, D X W X H (mm) | 369 x 190 x 318 | 369 x 190 x 318 |
| Long-run Model | Net Weight (kgs) | 14 | 15 |
| MANAGEMENT | |||
| Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC | |
General
CAPACITY
| Galleon III 6K(L*) | 6000 VA / 6000 W |
|---|---|
| Galleon III 10K(L*) | 10000 VA / 10000 W |
PHASE
| Galleon III 6K(L*) | 1 phase in / 1 phase out |
|---|---|
| Galleon III 10K(L*) | 1 phase in / 1 phase out |
INPUT
Voltage Range
| Galleon III 6K(L*) | 110~300VAC ± 3 % at 60% load 176~300VAC ± 3 % at 100% load |
|---|---|
| Galleon III 10K(L*) | 110~300VAC ± 3 % at 60% load 176~300VAC ± 3 % at 100% load |
Nominal Voltage
| Galleon III 6K(L*) | 208/220/230/240 VAC |
|---|---|
| Galleon III 10K(L*) | 208/220/230/240 VAC |
Frequency Range
| Galleon III 6K(L*) | 46~54 Hz or 56~64 Hz 40 ~ 70 Hz (In generator mode) |
|---|---|
| Galleon III 10K(L*) | 46~54 Hz or 56~64 Hz 40 ~ 70 Hz (In generator mode) |
Power Factor
| Galleon III 6K(L*) | ≧ 0.99 @ full load |
|---|---|
| Galleon III 10K(L*) | ≧ 0.99 @ full load |
THDi
| Galleon III 6K(L*) | <4% @100% Load |
|---|---|
| Galleon III 10K(L*) | <4% @100% Load |
OUTPUT
Output Voltage
| Galleon III 6K(L*) | 208*/220/230/240 VAC |
|---|---|
| Galleon III 10K(L*) | 208*/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode)
| Galleon III 6K(L*) | ± 1% |
|---|---|
| Galleon III 10K(L*) | ± 1% |
Frequency Range (Batt. Mode)
| Galleon III 6K(L*) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
|---|---|
| Galleon III 10K(L*) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Transfer Time AC Mode to Batt. Mode
| Galleon III 6K(L*) | Zero |
|---|---|
| Galleon III 10K(L*) | Zero |
Transfer Time Inverter to Bypass
| Galleon III 6K(L*) | zero |
|---|---|
| Galleon III 10K(L*) | zero |
Waveform (Batt. Mode)
| Galleon III 6K(L*) | Pure Sinewave |
|---|---|
| Galleon III 10K(L*) | Pure Sinewave |
Current Crest Ratio
| Galleon III 6K(L*) | 3:1 (max.) |
|---|---|
| Galleon III 10K(L*) | 3:1 (max.) |
Harmonic Distortion
| Galleon III 6K(L*) | ≦1 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) |
|---|---|
| Galleon III 10K(L*) | ≦1 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) |
Frequency Range (Synchronized Range)
| Galleon III 6K(L*) | 46~54 Hz or 56~64 Hz |
|---|---|
| Galleon III 10K(L*) | 46~54 Hz or 56~64 Hz |
Overload AC Mode
| Galleon III 6K(L*) | 100-110% for 60 min, 110-125% for 10 min, 125%~150% 1min, >150% transfer to bypass |
|---|---|
| Galleon III 10K(L*) | 100-110% for 60 min, 110-125% for 10 min, 125%~150% 1min, >150% transfer to bypass |
Overload Battery Mode
| Galleon III 6K(L*) | 100-110% for 3 min, 110-130% for 30s ,>130% immediately |
|---|---|
| Galleon III 10K(L*) | 100-110% for 3 min, 110-130% for 30s ,>130% immediately |
EFFICIENCY
Battery Mode
| Galleon III 6K(L*) | 0.92 |
|---|---|
| Galleon III 10K(L*) | 0.92 |
AC Mode
| Galleon III 6K(L*) | 0.95 |
|---|---|
| Galleon III 10K(L*) | 0.95 |
BATTERY
Long-run Model Battery Type
| Galleon III 6K(L*) | Depending on applications |
|---|---|
| Galleon III 10K(L*) | Depending on applications |
Long-run Model Charging Current (max.)
| Galleon III 6K(L*) | 2A (Default) ,1A/2A/4A/6A/8A adjustable |
|---|---|
| Galleon III 10K(L*) | 2A (Default) ,1A/2A/4A/6A/8A adjustable |
Long-run Model Charging Voltage
| Galleon III 6K(L*) | (13.65VDC x battery number) ± 1% |
|---|---|
| Galleon III 10K(L*) | (13.65VDC x battery number) ± 1% |
Long-run Model Numbers
| Galleon III 6K(L*) | 16-20** |
|---|---|
| Galleon III 10K(L*) | 16-20** |
Standard Model Battery Type
| Galleon III 6K(L*) | 12 V / 7 AH |
|---|---|
| Galleon III 10K(L*) | 12 V / 9 AH |
Standard Model Charging Current (max.)
| Galleon III 6K(L*) | 1.0 A |
|---|---|
| Galleon III 10K(L*) | 1.0 A |
Standard Model Charging Voltage
| Galleon III 6K(L*) | 218.4 VDC ± 1% |
|---|---|
| Galleon III 10K(L*) | 273 VDC ± 1% |
Standard Model Numbers
| Galleon III 6K(L*) | 16 |
|---|---|
| Galleon III 10K(L*) | 20 |
Standard Model Typical Recharge Time
| Galleon III 6K(L*) | 7 hours recover to 90% capacity |
|---|---|
| Galleon III 10K(L*) | 9 hours recover to 90% capacity |
ENVIRONMENT
Noise Level
| Galleon III 6K(L*) | Less than 55dBA @ 1 Meter |
|---|---|
| Galleon III 10K(L*) | Less than 58dB @ 1 Meter |
Operation Humidity
| Galleon III 6K(L*) | > 95% RH @ 0- 40°C (non-condensing) |
|---|---|
| Galleon III 10K(L*) | > 95% RH @ 0- 40°C (non-condensing) |
PHYSICAL
Standard Model Dimension, D X W X H (mm)
| Galleon III 6K(L*) | 369 x 190 x 688 |
|---|---|
| Galleon III 10K(L*) | 442 x 190 x 688 |
Standard Model Net Weight (kgs)
| Galleon III 6K(L*) | 55 |
|---|---|
| Galleon III 10K(L*) | 74 |
Long-run Model Dimension, D X W X H (mm)
| Galleon III 6K(L*) | 369 x 190 x 318 |
|---|---|
| Galleon III 10K(L*) | 369 x 190 x 318 |
Long-run Model Net Weight (kgs)
| Galleon III 6K(L*) | 14 |
|---|---|
| Galleon III 10K(L*) | 15 |
MANAGEMENT
Optional SNMP
| Galleon III 6K(L*) | Power management from SNMP manager and web browser |
|---|---|
| Galleon III 10K(L*) | Power management from SNMP manager and web browser |
Smart RS-232 / USB
| Galleon III 6K(L*) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC |
|---|---|
| Galleon III 10K(L*) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC |
| Brochure | Galleon III 6KVA-10KVA | |
| Manual | Galleon III-TOWER-6KL-10KL-manual |
Single phase - Online UPS Galleon III 6KVA/10KVA Exceptional Energy-Efficient UPS