Galleon II Rackmount/Rack Tower
2U 1KVA-3KVA Online UPS
Galleon II 1K-3K provides better output power factor up to 0.9 with higher performance and efficiency for critical applications. It’s same as Galleon series with programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devices. This Galleon II 1K-3K series is also suitable for laser printer and ultrasound system load.
Main Features
- True double-conversion
- Output power factor 0.9
- ECO and advanced ECO mode for energy saving
- Output voltage regulation < 1%
- Higher output crest radio 3:1
- 50Hz/60Hz frequency converter mode
- Programmable power management outlets
- Emergency power off function (EPO)
- Hot swappable battery design
MODEL | Galleon II RM 1K | Galleon II RM 1.5K | Galleon II RM 2K | Galleon II RM 3K | |
CAPACITY | 1000 VA / 900 W | 1500 VA / 1350 W | 2000 VA / 1800 W | 3000 VA / 2700 W | |
PHASE | Single phase with ground | Single phase with ground | Single phase with ground | Single phase with ground | |
INPUT | |||||
Voltage Range | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | |
Nominal Voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | |
Frequency Range | 40Hz~70Hz | 40Hz~70Hz | 40Hz~70Hz | 40Hz~70Hz | |
Power Factor | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | |
Harmonic Distortion (THDi) | ≦ 5% @ nominal input voltage | ≦ 5% @ nominal input voltage | ≦ 5% @ nominal input voltage | ≦ 5% @ nominal input voltage | |
OUTPUT | |||||
Output Voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | |
AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% | ± 1% | ± 1% | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
Transfer Time | AC Mode to Battery Mode | Zero | Zero | Zero | Zero |
Transfer Time | Inverter to Bypass | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) |
Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | |
Current Crest Ratio | 3:1 (max.) | 3:1 (max.) | 3:1 (max.) | 3:1 (max.) | |
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) | |
Frequency Range (Synchronized Range) | 57~63 Hz or 47~53 Hz | 57~63 Hz or 47~53 Hz | 57~63 Hz or 47~53 Hz | 57~63 Hz or 47~53 Hz | |
EFFICIENCY | |||||
Battery Mode | 88%,89% | 89% | 88%, 89% | 90% | |
ECO Mode | 97% | 97% | 97% | 97% | |
AC Mode | 90% | 90% | 91% | 91% | |
BATTERY | |||||
Long-run Model | Model-Battery Type | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries |
Long-run Model | Model-Charging Current (max.) | 1A / 2A / 4A / 8A (Selectable via LCD Setting) | 1A / 2A / 4A / 8A (Selectable via LCD Setting) | 1A / 2A / 4A / 8A (Selectable via LCD Setting) | 1A / 2A / 4A / 8A (Selectable via LCD Setting) |
Long-run Model | Model-Charging Voltage | 27.4 VDC ± 1%, 41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ± 1%, 82.1 VDC ± 1% | 82.1 VDC ± 1% |
Long-run Model | Model-Numbers | 2,3 | 3 | 4.6 | 6 |
Standard Model | Battery Type | 12 V / 9 AH, 12 V / 7 AH | 12 V / 9 AH | 12 V / 9 AH,12 V / 7 AH | 12 V / 9 AH |
Standard Model | Charging Current (max.) | 1.5 A | 1.5 A | 1.5 A | 1.5 A |
Standard Model | Charging Voltage | 27.4 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ± 1%, 82.1 VDC ± 1% | 82.1 VDC ± 1% |
Standard Model | Numbers | 2,3 | 3 | 4, 6 | 6 |
Standard Model | Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
INDICATORS | |||||
LCD Display | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators | |
ALARM | |||||
Battery Mode | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | |
Low Battery | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | |
Overload | Sounding every second | Sounding every second | Sounding every second | Sounding every second | |
Fault | Continuously sounding | Continuously sounding | Continuously sounding | Continuously sounding | |
ENVIRONMENT | |||||
Operating Humidity | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | 20~90% RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | |
PHYSICAL | |||||
Standard Model | Dimension, D X W X H (mm) | 410 x 438 x 88 | 410 x 438 x 88 | 510 x 438 x 88, 630 x 438 x 88 | 630 x 438 x 88 |
Standard Model | Net Weight (kgs) | 11.6, 14.2 | 14.5 | 19.5, 26.9 | 27.4 |
Long-run Model | Dimension, D X W X H (mm) | 410 x 438 x 88 | 410 x 438 x 88 | 410 x 438 x 88 | 510 x 438 x 88 |
Long-run Model | Net Weight (kgs) | 6.4 | 6.5 | 6.5 | 10.5 |
MANAGEMENT | |||||
Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
General
CAPACITY
Galleon II RM 1K | 1000 VA / 900 W |
---|---|
Galleon II RM 1.5K | 1500 VA / 1350 W |
Galleon II RM 2K | 2000 VA / 1800 W |
Galleon II RM 3K | 3000 VA / 2700 W |
PHASE
Galleon II RM 1K | Single phase with ground |
---|---|
Galleon II RM 1.5K | Single phase with ground |
Galleon II RM 2K | Single phase with ground |
Galleon II RM 3K | Single phase with ground |
INPUT
Voltage Range
Galleon II RM 1K | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
---|---|
Galleon II RM 1.5K | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Galleon II RM 2K | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Galleon II RM 3K | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Nominal Voltage
Galleon II RM 1K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon II RM 1.5K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II RM 2K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II RM 3K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Frequency Range
Galleon II RM 1K | 40Hz~70Hz |
---|---|
Galleon II RM 1.5K | 40Hz~70Hz |
Galleon II RM 2K | 40Hz~70Hz |
Galleon II RM 3K | 40Hz~70Hz |
Power Factor
Galleon II RM 1K | ≧ 0.99 @ Nominal Voltage (100% load) |
---|---|
Galleon II RM 1.5K | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon II RM 2K | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon II RM 3K | ≧ 0.99 @ Nominal Voltage (100% load) |
Harmonic Distortion (THDi)
Galleon II RM 1K | ≦ 5% @ nominal input voltage |
---|---|
Galleon II RM 1.5K | ≦ 5% @ nominal input voltage |
Galleon II RM 2K | ≦ 5% @ nominal input voltage |
Galleon II RM 3K | ≦ 5% @ nominal input voltage |
OUTPUT
Output Voltage
Galleon II RM 1K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon II RM 1.5K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II RM 2K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II RM 3K | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode)
Galleon II RM 1K | ± 1% |
---|---|
Galleon II RM 1.5K | ± 1% |
Galleon II RM 2K | ± 1% |
Galleon II RM 3K | ± 1% |
Frequency Range (Batt. Mode)
Galleon II RM 1K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
---|---|
Galleon II RM 1.5K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon II RM 2K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon II RM 3K | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Transfer Time AC Mode to Battery Mode
Galleon II RM 1K | Zero |
---|---|
Galleon II RM 1.5K | Zero |
Galleon II RM 2K | Zero |
Galleon II RM 3K | Zero |
Transfer Time Inverter to Bypass
Galleon II RM 1K | 4 ms (Typical) |
---|---|
Galleon II RM 1.5K | 4 ms (Typical) |
Galleon II RM 2K | 4 ms (Typical) |
Galleon II RM 3K | 4 ms (Typical) |
Waveform (Batt. Mode)
Galleon II RM 1K | Pure Sine Wave |
---|---|
Galleon II RM 1.5K | Pure Sine Wave |
Galleon II RM 2K | Pure Sine Wave |
Galleon II RM 3K | Pure Sine Wave |
Current Crest Ratio
Galleon II RM 1K | 3:1 (max.) |
---|---|
Galleon II RM 1.5K | 3:1 (max.) |
Galleon II RM 2K | 3:1 (max.) |
Galleon II RM 3K | 3:1 (max.) |
Harmonic Distortion
Galleon II RM 1K | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) |
---|---|
Galleon II RM 1.5K | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) |
Galleon II RM 2K | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) |
Galleon II RM 3K | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear load) |
Frequency Range (Synchronized Range)
Galleon II RM 1K | 57~63 Hz or 47~53 Hz |
---|---|
Galleon II RM 1.5K | 57~63 Hz or 47~53 Hz |
Galleon II RM 2K | 57~63 Hz or 47~53 Hz |
Galleon II RM 3K | 57~63 Hz or 47~53 Hz |
EFFICIENCY
Battery Mode
Galleon II RM 1K | 88%,89% |
---|---|
Galleon II RM 1.5K | 89% |
Galleon II RM 2K | 88%, 89% |
Galleon II RM 3K | 90% |
ECO Mode
Galleon II RM 1K | 97% |
---|---|
Galleon II RM 1.5K | 97% |
Galleon II RM 2K | 97% |
Galleon II RM 3K | 97% |
AC Mode
Galleon II RM 1K | 90% |
---|---|
Galleon II RM 1.5K | 90% |
Galleon II RM 2K | 91% |
Galleon II RM 3K | 91% |
BATTERY
Long-run Model Model-Battery Type
Galleon II RM 1K | Depending on the capacity of external batteries |
---|---|
Galleon II RM 1.5K | Depending on the capacity of external batteries |
Galleon II RM 2K | Depending on the capacity of external batteries |
Galleon II RM 3K | Depending on the capacity of external batteries |
Long-run Model Model-Charging Current (max.)
Galleon II RM 1K | 1A / 2A / 4A / 8A (Selectable via LCD Setting) |
---|---|
Galleon II RM 1.5K | 1A / 2A / 4A / 8A (Selectable via LCD Setting) |
Galleon II RM 2K | 1A / 2A / 4A / 8A (Selectable via LCD Setting) |
Galleon II RM 3K | 1A / 2A / 4A / 8A (Selectable via LCD Setting) |
Long-run Model Model-Charging Voltage
Galleon II RM 1K | 27.4 VDC ± 1%, 41.1 VDC ± 1% |
---|---|
Galleon II RM 1.5K | 41.1 VDC ± 1% |
Galleon II RM 2K | 54.8 VDC ± 1%, 82.1 VDC ± 1% |
Galleon II RM 3K | 82.1 VDC ± 1% |
Long-run Model Model-Numbers
Galleon II RM 1K | 2,3 |
---|---|
Galleon II RM 1.5K | 3 |
Galleon II RM 2K | 4.6 |
Galleon II RM 3K | 6 |
Standard Model Battery Type
Galleon II RM 1K | 12 V / 9 AH, 12 V / 7 AH |
---|---|
Galleon II RM 1.5K | 12 V / 9 AH |
Galleon II RM 2K | 12 V / 9 AH,12 V / 7 AH |
Galleon II RM 3K | 12 V / 9 AH |
Standard Model Charging Current (max.)
Galleon II RM 1K | 1.5 A |
---|---|
Galleon II RM 1.5K | 1.5 A |
Galleon II RM 2K | 1.5 A |
Galleon II RM 3K | 1.5 A |
Standard Model Charging Voltage
Galleon II RM 1K | 27.4 VDC ± 1% |
---|---|
Galleon II RM 1.5K | 41.1 VDC ± 1% |
Galleon II RM 2K | 54.8 VDC ± 1%, 82.1 VDC ± 1% |
Galleon II RM 3K | 82.1 VDC ± 1% |
Standard Model Numbers
Galleon II RM 1K | 2,3 |
---|---|
Galleon II RM 1.5K | 3 |
Galleon II RM 2K | 4, 6 |
Galleon II RM 3K | 6 |
Standard Model Typical Recharge Time
Galleon II RM 1K | 4 hours recover to 90% capacity |
---|---|
Galleon II RM 1.5K | 4 hours recover to 90% capacity |
Galleon II RM 2K | 4 hours recover to 90% capacity |
Galleon II RM 3K | 4 hours recover to 90% capacity |
INDICATORS
LCD Display
Galleon II RM 1K | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators |
---|---|
Galleon II RM 1.5K | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators |
Galleon II RM 2K | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators |
Galleon II RM 3K | UPS Status, Load level, Battery leve, Battery mode, Input/Output voltage, Discharge timer, and Fault indicators |
ALARM
Battery Mode
Galleon II RM 1K | Sounding every 5 seconds |
---|---|
Galleon II RM 1.5K | Sounding every 5 seconds |
Galleon II RM 2K | Sounding every 5 seconds |
Galleon II RM 3K | Sounding every 5 seconds |
Low Battery
Galleon II RM 1K | Sounding every 2 seconds |
---|---|
Galleon II RM 1.5K | Sounding every 2 seconds |
Galleon II RM 2K | Sounding every 2 seconds |
Galleon II RM 3K | Sounding every 2 seconds |
Overload
Galleon II RM 1K | Sounding every second |
---|---|
Galleon II RM 1.5K | Sounding every second |
Galleon II RM 2K | Sounding every second |
Galleon II RM 3K | Sounding every second |
Fault
Galleon II RM 1K | Continuously sounding |
---|---|
Galleon II RM 1.5K | Continuously sounding |
Galleon II RM 2K | Continuously sounding |
Galleon II RM 3K | Continuously sounding |
ENVIRONMENT
Operating Humidity
Galleon II RM 1K | 20~90% RH @ 0- 40°C (non-condensing) |
---|---|
Galleon II RM 1.5K | 20~90% RH @ 0- 40°C (non-condensing) |
Galleon II RM 2K | 20~90% RH @ 0- 40°C (non-condensing) |
Galleon II RM 3K | 20~90% RH @ 0- 40°C (non-condensing) |
Noise Level
Galleon II RM 1K | Less than 50dB @ 1 Meter |
---|---|
Galleon II RM 1.5K | Less than 50dB @ 1 Meter |
Galleon II RM 2K | Less than 50dB @ 1 Meter |
Galleon II RM 3K | Less than 50dB @ 1 Meter |
PHYSICAL
Standard Model Dimension, D X W X H (mm)
Galleon II RM 1K | 410 x 438 x 88 |
---|---|
Galleon II RM 1.5K | 410 x 438 x 88 |
Galleon II RM 2K | 510 x 438 x 88, 630 x 438 x 88 |
Galleon II RM 3K | 630 x 438 x 88 |
Standard Model Net Weight (kgs)
Galleon II RM 1K | 11.6, 14.2 |
---|---|
Galleon II RM 1.5K | 14.5 |
Galleon II RM 2K | 19.5, 26.9 |
Galleon II RM 3K | 27.4 |
Long-run Model Dimension, D X W X H (mm)
Galleon II RM 1K | 410 x 438 x 88 |
---|---|
Galleon II RM 1.5K | 410 x 438 x 88 |
Galleon II RM 2K | 410 x 438 x 88 |
Galleon II RM 3K | 510 x 438 x 88 |
Long-run Model Net Weight (kgs)
Galleon II RM 1K | 6.4 |
---|---|
Galleon II RM 1.5K | 6.5 |
Galleon II RM 2K | 6.5 |
Galleon II RM 3K | 10.5 |
MANAGEMENT
Optional SNMP
Galleon II RM 1K | Power management from SNMP manager and web browser |
---|---|
Galleon II RM 1.5K | Power management from SNMP manager and web browser |
Galleon II RM 2K | Power management from SNMP manager and web browser |
Galleon II RM 3K | Power management from SNMP manager and web browser |
Smart RS-232/USB
Galleon II RM 1K | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
---|---|
Galleon II RM 1.5K | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
Galleon II RM 2K | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
Galleon II RM 3K | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC |
Brochure | Galleon II_Brochure | |
Manual | Galleon II RM_1-3K_Manual |