- Select Capacity
- Galleon II 1K (L)
- Galleon II 1.5K (L)
- Galleon II 2K (L)
- Galleon II 3K (L)
- Select Capacity
- Galleon II 1K (L)
- Galleon II 1.5K (L)
- Galleon II 2K (L)
- Galleon II 3K (L)
12
Galleon II 1K-3KVA
PF0.9 Online UPS with wide input voltage range
Galleon II 1K-3K provides better output power factor up to 0.9 with higher performance and efficiency for critical applications. It’s same as Galleon series with programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devices. This Galleon II 1K-3K series is also suitable for laser printer and ultrasound system load.


Main Features
- True double-conversion online UPS
- Wide input voltage range (110-300 VAC, 55-150 VAC)
- Input power factor correction 0.99
- Output power factor 0.9
- 50/60 Hz Frequency Converter Mode
- Programmable power management outlets
- Emergency power off function (EPO)
- ECO mode operation for energy saving
- Very high surge immunity up to 7KV, 13KA, 1300J
- Generator compatible
- High overload capability and enhanced short circuit protection
- SNMP/USB/RS-232 multiple communications
- 3-stage smart charging design
- Maximum 8A extended parallel control available for long run model
- Selectable output voltage: 200-240VAC, 100-127VAC
- Laser printer and ultrasound system load acceptable
MODEL | Galleon II 1K (L) | Galleon II 1.5K (L) | Galleon II 2K (L) | Galleon II 3K (L) | |
CAPACITY | 1000 VA / 900 W | 1500 VA / 1350 W | 2000 VA / 1800 W | 3000 VA / 2700 W | |
PHASE | Single phase with ground | Single phase with ground | Single phase with ground | Single phase with ground | |
INPUT | |||||
Voltage Range | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | |
Nominal Voltage | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | |
Frequency Range | 40 Hz~70 Hz | 40 Hz~70 Hz | 40 Hz~70 Hz | 40 Hz~70 Hz | |
Power Factor | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | ≧ 0.99 @ Nominal Voltage (100% load) | |
Harmonic Distortion (THDi) | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged | |
OUTPUT | |||||
Output Voltage | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC | |
AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% | ± 1% | ± 1% | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
Transfer Time | AC Mode to Battery Mode | Zero | Zero | Zero | Zero |
Transfer Time | Inverter to Bypass | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) | 4 ms (Typical) |
Waveform (Batt. Mode) | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | Pure Sine Wave | |
Current Crest Ratio | 3:1 | 3:1 | 3:1 | 3:1 | |
Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | |
Frequency Range (Synchronized Range) | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | 47~53 Hz or 57~63 Hz | |
EFFICIENCY | |||||
Battery Mode | 89% | 89% | 89% | 90% | |
ECO Mode | 97% | 97% | 97% | 97% | |
AC Mode | 90% | 90% | 91% | 91% | |
BATTERY | |||||
Long-run Model | Model-Battery Type | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries | Depending on the capacity of external batteries |
Long-run Model | Model-Charging Current (max.) | 1A/2A/4A/6A/8A (Selectable) | 1A/2A/4A/6A/8A (Selectable) | 1A/2A/4A/6A/8A (Selectable) | 1A/2A/4A/6A/7A (Selectable) |
Long-run Model | Model-Charging Voltage | 41.0 VDC ± 1% | 41.0 VDC ± 1% | 82.1 VDC ± 1% | 82.1 VDC ± 1% ,109.6 VDC ± 1% |
Long-run Model | Model-Numbers | 3 | 3 | 6 | 6,8 |
Standard Model | Battery Type | 12 V / 7 Ah | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah |
Standard Model | Charging Current (max.) | 1.5 A | 1.5 A | 1.5 A | 1.5 A |
Standard Model | Charging Voltage | 41.0 VDC ± 1% | 41.0 VDC ± 1% | 82.1 VDC ± 1% | 82.1 VDC ± 1%, 109.6 VDC ± 1% |
Standard Model | Numbers | 3 | 3 | 6 | 6, 8 |
Standard Model | Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
INDICATORS | |||||
LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
ALARM | |||||
Battery Mode | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | Sounding every 5 seconds | |
Low Battery | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | Sounding every 2 seconds | |
Overload | Sounding every second | Sounding every second | Sounding every second | Sounding every second | |
Fault | Continuously sounding | Continuously sounding | Continuously sounding | Continuously sounding | |
ENVIRONMENT | |||||
Operating Humidity | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | 20~95% RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | Less than 50dB @ 1 Meter | |
PHYSICAL | |||||
Standard Model | Dimension, D X W X H (mm) | 397 X 145 X 220 | 397 X 145 X 220 | 421 X 190 X 318 | 421 X 190 X 318 |
Standard Model | Net Weight (kgs) | 12 | 13.8 | 22.5 | 26.6,32.2 |
Long-run Model | Dimension, D X W X H (mm) | 397 X 145 X 220 | 397 X 145 X 220 | 421 X 190 X 318 | 421 X 190 X 318 |
Long-run Model | Net Weight (kgs) | 6.3 | 6.5 | 10.5 | 11.7 |
MANAGEMENT | |||||
Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | |
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
General
CAPACITY
Galleon II 1K (L) | 1000 VA / 900 W |
---|---|
Galleon II 1.5K (L) | 1500 VA / 1350 W |
Galleon II 2K (L) | 2000 VA / 1800 W |
Galleon II 3K (L) | 3000 VA / 2700 W |
PHASE
Galleon II 1K (L) | Single phase with ground |
---|---|
Galleon II 1.5K (L) | Single phase with ground |
Galleon II 2K (L) | Single phase with ground |
Galleon II 3K (L) | Single phase with ground |
INPUT
Voltage Range
Galleon II 1K (L) | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
---|---|
Galleon II 1.5K (L) | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Galleon II 2K (L) | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Galleon II 3K (L) | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load; 80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load |
Nominal Voltage
Galleon II 1K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon II 1.5K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II 2K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II 3K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
Frequency Range
Galleon II 1K (L) | 40 Hz~70 Hz |
---|---|
Galleon II 1.5K (L) | 40 Hz~70 Hz |
Galleon II 2K (L) | 40 Hz~70 Hz |
Galleon II 3K (L) | 40 Hz~70 Hz |
Power Factor
Galleon II 1K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
---|---|
Galleon II 1.5K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon II 2K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
Galleon II 3K (L) | ≧ 0.99 @ Nominal Voltage (100% load) |
Harmonic Distortion (THDi)
Galleon II 1K (L) | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged |
---|---|
Galleon II 1.5K (L) | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged |
Galleon II 2K (L) | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged |
Galleon II 3K (L) | ≦ 5% @100~130VAC or 205-245VAC; THDU < 1.6% @ input and full linear load condition with battery fully charged |
OUTPUT
Output Voltage
Galleon II 1K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
---|---|
Galleon II 1.5K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II 2K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
Galleon II 3K (L) | 100/110/115/120/127 VAC or 200/208/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode)
Galleon II 1K (L) | ± 1% |
---|---|
Galleon II 1.5K (L) | ± 1% |
Galleon II 2K (L) | ± 1% |
Galleon II 3K (L) | ± 1% |
Frequency Range (Batt. Mode)
Galleon II 1K (L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
---|---|
Galleon II 1.5K (L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon II 2K (L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Galleon II 3K (L) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Transfer Time AC Mode to Battery Mode
Galleon II 1K (L) | Zero |
---|---|
Galleon II 1.5K (L) | Zero |
Galleon II 2K (L) | Zero |
Galleon II 3K (L) | Zero |
Transfer Time Inverter to Bypass
Galleon II 1K (L) | 4 ms (Typical) |
---|---|
Galleon II 1.5K (L) | 4 ms (Typical) |
Galleon II 2K (L) | 4 ms (Typical) |
Galleon II 3K (L) | 4 ms (Typical) |
Waveform (Batt. Mode)
Galleon II 1K (L) | Pure Sine Wave |
---|---|
Galleon II 1.5K (L) | Pure Sine Wave |
Galleon II 2K (L) | Pure Sine Wave |
Galleon II 3K (L) | Pure Sine Wave |
Current Crest Ratio
Galleon II 1K (L) | 3:1 |
---|---|
Galleon II 1.5K (L) | 3:1 |
Galleon II 2K (L) | 3:1 |
Galleon II 3K (L) | 3:1 |
Harmonic Distortion
Galleon II 1K (L) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) |
---|---|
Galleon II 1.5K (L) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) |
Galleon II 2K (L) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) |
Galleon II 3K (L) | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) |
Frequency Range (Synchronized Range)
Galleon II 1K (L) | 47~53 Hz or 57~63 Hz |
---|---|
Galleon II 1.5K (L) | 47~53 Hz or 57~63 Hz |
Galleon II 2K (L) | 47~53 Hz or 57~63 Hz |
Galleon II 3K (L) | 47~53 Hz or 57~63 Hz |
EFFICIENCY
Battery Mode
Galleon II 1K (L) | 89% |
---|---|
Galleon II 1.5K (L) | 89% |
Galleon II 2K (L) | 89% |
Galleon II 3K (L) | 90% |
ECO Mode
Galleon II 1K (L) | 97% |
---|---|
Galleon II 1.5K (L) | 97% |
Galleon II 2K (L) | 97% |
Galleon II 3K (L) | 97% |
AC Mode
Galleon II 1K (L) | 90% |
---|---|
Galleon II 1.5K (L) | 90% |
Galleon II 2K (L) | 91% |
Galleon II 3K (L) | 91% |
BATTERY
Long-run Model Model-Battery Type
Galleon II 1K (L) | Depending on the capacity of external batteries |
---|---|
Galleon II 1.5K (L) | Depending on the capacity of external batteries |
Galleon II 2K (L) | Depending on the capacity of external batteries |
Galleon II 3K (L) | Depending on the capacity of external batteries |
Long-run Model Model-Charging Current (max.)
Galleon II 1K (L) | 1A/2A/4A/6A/8A (Selectable) |
---|---|
Galleon II 1.5K (L) | 1A/2A/4A/6A/8A (Selectable) |
Galleon II 2K (L) | 1A/2A/4A/6A/8A (Selectable) |
Galleon II 3K (L) | 1A/2A/4A/6A/7A (Selectable) |
Long-run Model Model-Charging Voltage
Galleon II 1K (L) | 41.0 VDC ± 1% |
---|---|
Galleon II 1.5K (L) | 41.0 VDC ± 1% |
Galleon II 2K (L) | 82.1 VDC ± 1% |
Galleon II 3K (L) | 82.1 VDC ± 1% ,109.6 VDC ± 1% |
Long-run Model Model-Numbers
Galleon II 1K (L) | 3 |
---|---|
Galleon II 1.5K (L) | 3 |
Galleon II 2K (L) | 6 |
Galleon II 3K (L) | 6,8 |
Standard Model Battery Type
Galleon II 1K (L) | 12 V / 7 Ah |
---|---|
Galleon II 1.5K (L) | 12 V / 9 Ah |
Galleon II 2K (L) | 12 V / 7 Ah |
Galleon II 3K (L) | 12 V / 9 Ah |
Standard Model Charging Current (max.)
Galleon II 1K (L) | 1.5 A |
---|---|
Galleon II 1.5K (L) | 1.5 A |
Galleon II 2K (L) | 1.5 A |
Galleon II 3K (L) | 1.5 A |
Standard Model Charging Voltage
Galleon II 1K (L) | 41.0 VDC ± 1% |
---|---|
Galleon II 1.5K (L) | 41.0 VDC ± 1% |
Galleon II 2K (L) | 82.1 VDC ± 1% |
Galleon II 3K (L) | 82.1 VDC ± 1%, 109.6 VDC ± 1% |
Standard Model Numbers
Galleon II 1K (L) | 3 |
---|---|
Galleon II 1.5K (L) | 3 |
Galleon II 2K (L) | 6 |
Galleon II 3K (L) | 6, 8 |
Standard Model Typical Recharge Time
Galleon II 1K (L) | 4 hours recover to 90% capacity |
---|---|
Galleon II 1.5K (L) | 4 hours recover to 90% capacity |
Galleon II 2K (L) | 4 hours recover to 90% capacity |
Galleon II 3K (L) | 4 hours recover to 90% capacity |
INDICATORS
LCD Panel
Galleon II 1K (L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
---|---|
Galleon II 1.5K (L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
Galleon II 2K (L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
Galleon II 3K (L) | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
ALARM
Battery Mode
Galleon II 1K (L) | Sounding every 5 seconds |
---|---|
Galleon II 1.5K (L) | Sounding every 5 seconds |
Galleon II 2K (L) | Sounding every 5 seconds |
Galleon II 3K (L) | Sounding every 5 seconds |
Low Battery
Galleon II 1K (L) | Sounding every 2 seconds |
---|---|
Galleon II 1.5K (L) | Sounding every 2 seconds |
Galleon II 2K (L) | Sounding every 2 seconds |
Galleon II 3K (L) | Sounding every 2 seconds |
Overload
Galleon II 1K (L) | Sounding every second |
---|---|
Galleon II 1.5K (L) | Sounding every second |
Galleon II 2K (L) | Sounding every second |
Galleon II 3K (L) | Sounding every second |
Fault
Galleon II 1K (L) | Continuously sounding |
---|---|
Galleon II 1.5K (L) | Continuously sounding |
Galleon II 2K (L) | Continuously sounding |
Galleon II 3K (L) | Continuously sounding |
ENVIRONMENT
Operating Humidity
Galleon II 1K (L) | 20~95% RH @ 0- 40°C (non-condensing) |
---|---|
Galleon II 1.5K (L) | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon II 2K (L) | 20~95% RH @ 0- 40°C (non-condensing) |
Galleon II 3K (L) | 20~95% RH @ 0- 40°C (non-condensing) |
Noise Level
Galleon II 1K (L) | Less than 50dB @ 1 Meter |
---|---|
Galleon II 1.5K (L) | Less than 50dB @ 1 Meter |
Galleon II 2K (L) | Less than 50dB @ 1 Meter |
Galleon II 3K (L) | Less than 50dB @ 1 Meter |
PHYSICAL
Standard Model Dimension, D X W X H (mm)
Galleon II 1K (L) | 397 X 145 X 220 |
---|---|
Galleon II 1.5K (L) | 397 X 145 X 220 |
Galleon II 2K (L) | 421 X 190 X 318 |
Galleon II 3K (L) | 421 X 190 X 318 |
Standard Model Net Weight (kgs)
Galleon II 1K (L) | 12 |
---|---|
Galleon II 1.5K (L) | 13.8 |
Galleon II 2K (L) | 22.5 |
Galleon II 3K (L) | 26.6,32.2 |
Long-run Model Dimension, D X W X H (mm)
Galleon II 1K (L) | 397 X 145 X 220 |
---|---|
Galleon II 1.5K (L) | 397 X 145 X 220 |
Galleon II 2K (L) | 421 X 190 X 318 |
Galleon II 3K (L) | 421 X 190 X 318 |
Long-run Model Net Weight (kgs)
Galleon II 1K (L) | 6.3 |
---|---|
Galleon II 1.5K (L) | 6.5 |
Galleon II 2K (L) | 10.5 |
Galleon II 3K (L) | 11.7 |
MANAGEMENT
Optional SNMP
Galleon II 1K (L) | Power management from SNMP manager and web browser |
---|---|
Galleon II 1.5K (L) | Power management from SNMP manager and web browser |
Galleon II 2K (L) | Power management from SNMP manager and web browser |
Galleon II 3K (L) | Power management from SNMP manager and web browser |
Smart RS-232 / USB
Galleon II 1K (L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
---|---|
Galleon II 1.5K (L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon II 2K (L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
Galleon II 3K (L) | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux, and MAC |
![]() |
Brochure | Galleon II_Brochure |
![]() |
Manual | Galleon II RM_1-3K_Manual |
![]() |
Manual | GalleonII-6-10K-Tower-RT-manual |
Single phase - Online UPS Galleon II 1K-3KVA PF0.9 Online UPS with wide input voltage range
Related Products
We have received your membership application and will reply as soon as within 24 hours, before that, please browse our website, thank you.