+Power Modular UPS
Maximum 300KW in single 42U cabinet
Offering high efficiency and overload capability, +Power is a truly modular UPS system which can easily scales in 30kW increments up to 210kW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.
Main Features
  • High efficiency online double conversion technology
  • High scalability
  • Unity output power factor
  • Modular design lowers MTTR
  • Highly reliable operation with redundant power supply in STS
  • User-adjustable charging current
  • Ease of installation and maintenance
  • Flexible battery configuration adapts different applications
  • High overload capability
  • Graphic 5.7” LCD design for easy management
  • N+1 or N+X parallel redundancy for power guarantee
  • Optional 10" touch LCD panel
General
CABINET CAPACITY
+Power 30U-90HV90KW
+Power 42U-120HV120KW
+Power 30U-80-20KHV120KW or 80KW
+Power 30U-120HV120KW or 80KW
+Power 30U-120-20KHV180KW or 120KW
+Power 30U-180HV180KW or 120KW
+Power 42U-200-20KHV200KW
+Power 42U-210HV210KW
+Power 42U-300HV300KW
PHASE
+Power 30U-90HV3-phase in/3-phase out
+Power 42U-120HV3-phase in/3-phase out
+Power 30U-80-20KHV3-phase in/3-phase out
+Power 30U-120HV3-phase in/3-phase out
+Power 30U-120-20KHV3-phase in/3-phase out
+Power 30U-180HV3-phase in/3-phase out
+Power 42U-200-20KHV3-phase in/3-phase out
+Power 42U-210HV3-phase in/3-phase out
+Power 42U-300HV3-phase in/3-phase out
Maximum Battery Set No.
+Power 30U-90HV3
+Power 42U-120HV5
+Power 30U-80-20KHV-
+Power 30U-120HV-
+Power 30U-120-20KHV-
+Power 30U-180HV-
+Power 42U-200-20KHV-
+Power 42U-210HV-
+Power 42U-300HV-
Battery Type
+Power 30U-90HVBuilt-in Battery
+Power 42U-120HVBuilt-in Battery
+Power 30U-80-20KHVExternal Battery
+Power 30U-120HVExternal Battery
+Power 30U-120-20KHVExternal Battery
+Power 30U-180HVExternal Battery
+Power 42U-200-20KHVExternal Battery
+Power 42U-210HVExternal Battery
+Power 42U-300HVExternal Battery
Maximum Power Module No.
+Power 30U-90HV3
+Power 42U-120HV4
+Power 30U-80-20KHV4
+Power 30U-120HV4
+Power 30U-120-20KHV6
+Power 30U-180HV6
+Power 42U-200-20KHV10
+Power 42U-210HV8
+Power 42U-300HV10
One Power Module Capacity
+Power 30U-90HV30 KVA / 30 KW
+Power 42U-120HV30 KVA / 30 KW
+Power 30U-80-20KHV30 KVA / 30 KW
+Power 30U-120HV30 KVA / 30 KW or 20 KVA / 20KW
+Power 30U-120-20KHV30 KVA / 30 KW or 20 KVA / 20KW
+Power 30U-180HV30 KVA / 30 KW or 20 KVA / 20KW
+Power 42U-200-20KHV20KW
+Power 42U-210HV30 KVA / 30 KW
+Power 42U-300HV30 KVA / 30 KW
INPUT
Voltage Range
+Power 30U-90HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 42U-120HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 30U-80-20KHV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 30U-120HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 30U-120-20KHV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 30U-180HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 42U-200-20KHV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 42U-210HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
+Power 42U-300HV305~478 VAC at 70%-100% load; 208~478VAC for <70% load
Nominal Voltage
+Power 30U-90HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-120HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-80-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-120HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-120-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-180HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-200-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-210HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-300HV3 x 380VAC/400VAC/415VAC (3Ph+N)
Frequency Range
+Power 30U-90HV40Hz ~70Hz
+Power 42U-120HV40Hz ~70Hz
+Power 30U-80-20KHV40Hz ~70Hz
+Power 30U-120HV40Hz ~70Hz
+Power 30U-120-20KHV40Hz ~70Hz
+Power 30U-180HV40Hz ~70Hz
+Power 42U-200-20KHV40Hz ~70Hz
+Power 42U-210HV40Hz ~70Hz
+Power 42U-300HV40Hz ~70Hz
Nominal Frequency
+Power 30U-90HV50/60 Hz (Auto sensing)
+Power 42U-120HV50/60 Hz (Auto sensing)
+Power 30U-80-20KHV50/60 Hz (Auto sensing)
+Power 30U-120HV50/60 Hz (Auto sensing)
+Power 30U-120-20KHV50/60 Hz (Auto sensing)
+Power 30U-180HV50/60 Hz (Auto sensing)
+Power 42U-200-20KHV50/60 Hz (Auto sensing)
+Power 42U-210HV50/60 Hz (Auto sensing)
+Power 42U-300HV50/60 Hz (Auto sensing)
Power Factor
+Power 30U-90HV> 0.99 at 100% load, >0.98 at 50% load
+Power 42U-120HV> 0.99 at 100% load, >0.98 at 50% load
+Power 30U-80-20KHV> 0.99 at 100% load, >0.98 at 50% load
+Power 30U-120HV> 0.99 at 100% load, >0.98 at 50% load
+Power 30U-120-20KHV> 0.99 at 100% load, >0.98 at 50% load
+Power 30U-180HV> 0.99 at 100% load, >0.98 at 50% load
+Power 42U-200-20KHV> 0.99 at 100% load, >0.98 at 50% load
+Power 42U-210HV> 0.99 at 100% load, >0.98 at 50% load
+Power 42U-300HV> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)
+Power 30U-90HV< 3% @ 100% load
+Power 42U-120HV< 3% @ 100% load
+Power 30U-80-20KHV< 3% @ 100% load
+Power 30U-120HV< 3% @ 100% load
+Power 30U-120-20KHV< 3% @ 100% load
+Power 30U-180HV< 3% @ 100% load
+Power 42U-200-20KHV< 3% @ 100% load
+Power 42U-210HV< 3% @ 100% load
+Power 42U-300HV< 3% @ 100% load
OUTPUT
Nominal Frequency
+Power 30U-90HV50/60Hz
+Power 42U-120HV50/60Hz
+Power 30U-80-20KHV50/60Hz
+Power 30U-120HV50/60Hz
+Power 30U-120-20KHV50/60Hz
+Power 30U-180HV50/60Hz
+Power 42U-200-20KHV50/60Hz
+Power 42U-210HV50/60Hz
+Power 42U-300HV50/60Hz
Overload Capability
+Power 30U-90HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 42U-120HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 30U-80-20KHV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 30U-120HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 30U-120-20KHV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 30U-180HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 42U-200-20KHV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 42U-210HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
+Power 42U-300HV1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150%
Voltage Regulation (Steady state)
+Power 30U-90HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 42U-120HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 30U-80-20KHV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 30U-120HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 30U-120-20KHV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 30U-180HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 42U-200-20KHV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 42U-210HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
+Power 42U-300HV≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load)
Nominal Voltage
+Power 30U-90HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-120HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-80-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-120HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-120-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 30U-180HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-200-20KHV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-210HV3 x 380VAC/400VAC/415VAC (3Ph+N)
+Power 42U-300HV3 x 380VAC/400VAC/415VAC (3Ph+N)
Efficiency
+Power 30U-90HVUp to 94.5%
+Power 42U-120HVUp to 94.5%
+Power 30U-80-20KHVUp to 94.5%
+Power 30U-120HVUp to 94.5%
+Power 30U-120-20KHVUp to 94.5%
+Power 30U-180HVUp to 94.5%
+Power 42U-200-20KHVUp to 94.5%
+Power 42U-210HVUp to 94.5%
+Power 42U-300HVUp to 94.5%
Harmonic Distortion
+Power 30U-90HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 42U-120HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 30U-80-20KHV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 30U-120HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 30U-120-20KHV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 30U-180HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 42U-200-20KHV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 42U-210HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
+Power 42U-300HV≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load)
Frequency Range (Synchronized range)
+Power 30U-90HV46Hz~54Hz or 56Hz~64Hz
+Power 42U-120HV46Hz~54Hz or 56Hz~64Hz
+Power 30U-80-20KHV46Hz~54Hz or 56Hz~64Hz
+Power 30U-120HV46Hz~54Hz or 56Hz~64Hz
+Power 30U-120-20KHV46Hz~54Hz or 56Hz~64Hz
+Power 30U-180HV46Hz~54Hz or 56Hz~64Hz
+Power 42U-200-20KHV46Hz~54Hz or 56Hz~64Hz
+Power 42U-210HV46Hz~54Hz or 56Hz~64Hz
+Power 42U-300HV46Hz~54Hz or 56Hz~64Hz
BATTERY & CHARGER
Floating Charge Voltage
+Power 30U-90HV2.25V/Cell
+Power 42U-120HV2.25V/Cell
+Power 30U-80-20KHV2.25V/Cell
+Power 30U-120HV2.25V/Cell
+Power 30U-120-20KHV2.25V/Cell
+Power 30U-180HV2.25V/Cell
+Power 42U-200-20KHV2.25V/Cell
+Power 42U-210HV2.25V/Cell
+Power 42U-300HV2.25V/Cell
Boost Charging Voltage
+Power 30U-90HV2.35V/Cell
+Power 42U-120HV2.35V/Cell
+Power 30U-80-20KHV2.35V/Cell
+Power 30U-120HV2.35V/Cell
+Power 30U-120-20KHV2.35V/Cell
+Power 30U-180HV2.35V/Cell
+Power 42U-200-20KHV2.35V/Cell
+Power 42U-210HV2.35V/Cell
+Power 42U-300HV2.35V/Cell
Maximum Charging Current
+Power 30U-90HV8A
+Power 42U-120HV8A
+Power 30U-80-20KHV8A for 30KW power module; 6A for 20KW power module
+Power 30U-120HV8A for 30KW power module; 6A for 20KW power module
+Power 30U-120-20KHV8A for 30KW power module; 6A for 20KW power module
+Power 30U-180HV8A for 30KW power module; 6A for 20KW power module
+Power 42U-200-20KHV6A
+Power 42U-210HV8A
+Power 42U-300HV8A
Maximum Voltage
+Power 30U-90HV+/- 240V (12V x 40 Pcs)
+Power 42U-120HV+/- 240V (12V x 40 Pcs)
+Power 30U-80-20KHV+/- 240V (12V x 40 Pcs)
+Power 30U-120HV+/- 240V (12V x 40 Pcs)
+Power 30U-120-20KHV+/- 240V (12V x 40 Pcs)
+Power 30U-180HV+/- 240V (12V x 40 Pcs)
+Power 42U-200-20KHV+/- 240V (12V x 40 Pcs)
+Power 42U-210HV+/- 240V (12V x 40 Pcs)
+Power 42U-300HV+/- 240V (12V x 40 Pcs)
Nominal Voltage
+Power 30U-90HV+/- 216V (12V x 36 Pcs)
+Power 42U-120HV+/- 216V (12V x 36 Pcs)
+Power 30U-80-20KHV+/- 216V (12V x 36 Pcs)
+Power 30U-120HV+/- 216V (12V x 36 Pcs)
+Power 30U-120-20KHV+/- 216V (12V x 36 Pcs)
+Power 30U-180HV+/- 216V (12V x 36 Pcs)
+Power 42U-200-20KHV+/- 216V (12V x 36 Pcs)
+Power 42U-210HV+/- 216V (12V x 36 Pcs)
+Power 42U-300HV+/- 216V (12V x 36 Pcs)
Temperature Compensation
+Power 30U-90HVYes
+Power 42U-120HVYes
+Power 30U-80-20KHVYes
+Power 30U-120HVYes
+Power 30U-120-20KHVYes
+Power 30U-180HVYes
+Power 42U-200-20KHVYes
+Power 42U-210HVYes
+Power 42U-300HVYes
Minimum Voltage
+Power 30U-90HV+/- 192V (12V x 32 Pcs)
+Power 42U-120HV+/- 192V (12V x 32 Pcs)
+Power 30U-80-20KHV+/- 192V (12V x 32 Pcs)
+Power 30U-120HV+/- 192V (12V x 32 Pcs)
+Power 30U-120-20KHV+/- 192V (12V x 32 Pcs)
+Power 30U-180HV+/- 192V (12V x 32 Pcs)
+Power 42U-200-20KHV+/- 192V (12V x 32 Pcs)
+Power 42U-210HV+/- 192V (12V x 32 Pcs)
+Power 42U-300HV+/- 192V (12V x 32 Pcs)
ENVIRONMENT
Altitude
+Power 30U-90HV<1000m for Nominal power
+Power 42U-120HV<1000m for Nominal power
+Power 30U-80-20KHV<1000m for Nominal power
+Power 30U-120HV<1000m for Nominal power
+Power 30U-120-20KHV<1000m for Nominal power
+Power 30U-180HV<1000m for Nominal power
+Power 42U-200-20KHV<1000m for Nominal power
+Power 42U-210HV<1000m for Nominal power
+Power 42U-300HV<1000m for Nominal power
IP Class
+Power 30U-90HVIP 20
+Power 42U-120HVIP 20
+Power 30U-80-20KHVIP 20
+Power 30U-120HVIP 20
+Power 30U-120-20KHVIP 20
+Power 30U-180HVIP 20
+Power 42U-200-20KHVIP 20
+Power 42U-210HVIP 20
+Power 42U-300HVIP 20
Operating Temperature
+Power 30U-90HV0~40℃
+Power 42U-120HV0~40℃
+Power 30U-80-20KHV0~40℃
+Power 30U-120HV0~40℃
+Power 30U-120-20KHV0~40℃
+Power 30U-180HV0~40℃
+Power 42U-200-20KHV0~40℃
+Power 42U-210HV0~40℃
+Power 42U-300HV0~40℃
Operating Humidity
+Power 30U-90HV0~95% non-condensing
+Power 42U-120HV0~95% non-condensing
+Power 30U-80-20KHV0~95% non-condensing
+Power 30U-120HV0~95% non-condensing
+Power 30U-120-20KHV0~95% non-condensing
+Power 30U-180HV0~95% non-condensing
+Power 42U-200-20KHV0~95% non-condensing
+Power 42U-210HV0~95% non-condensing
+Power 42U-300HV0~95% non-condensing
PHYSICAL
Cabinet Dimension (D x W x H) mm
+Power 30U-90HV1100 x 600 x 1475
+Power 42U-120HV1100 x 600 x 2010
+Power 30U-80-20KHV1100 x 600 x 1475
+Power 30U-120HV1100 x 600 x 1475
+Power 30U-120-20KHV1100 x 600 x 1475
+Power 30U-180HV1100 x 600 x 1475
+Power 42U-200-20KHV1100 x 600 x 2010
+Power 42U-210HV1100 x 600 x 2010
+Power 42U-300HV1100 x 600 x 2010
Net Weight (kgs)
+Power 30U-90HV675
+Power 42U-120HV932
+Power 30U-80-20KHV335 or 333
+Power 30U-120HV335 or 333
+Power 30U-120-20KHV437.5 or 434.5
+Power 30U-180HV437.5 or 434.5
+Power 42U-200-20KHV611
+Power 42U-210HV549
+Power 42U-300HV620
MANAGEMENT
Optional SNMP
+Power 30U-90HVPower management from SNMP manager and web browser
+Power 42U-120HVPower management from SNMP manager and web browser
+Power 30U-80-20KHVPower management from SNMP manager and web browser
+Power 30U-120HVPower management from SNMP manager and web browser
+Power 30U-120-20KHVPower management from SNMP manager and web browser
+Power 30U-180HVPower management from SNMP manager and web browser
+Power 42U-200-20KHVPower management from SNMP manager and web browser
+Power 42U-210HVPower management from SNMP manager and web browser
+Power 42U-300HVPower management from SNMP manager and web browser
Smart RS-232/USB
+Power 30U-90HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 42U-120HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 30U-80-20KHVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 30U-120HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 30U-120-20KHVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 30U-180HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 42U-200-20KHVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 42U-210HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
+Power 42U-300HVSupports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC
STANDARDS
Safety
+Power 30U-90HVIEC/EN 60950-1; IEC/EN 62040-1
+Power 42U-120HVIEC/EN 60950-1; IEC/EN 62040-1
+Power 30U-80-20KHVIEC/EN 60950-1; IEC/EN 62040-1
+Power 30U-120HVIEC/EN 60950-1; IEC/EN 62040-1
+Power 30U-120-20KHVIEC/EN 60950-1; IEC/EN 62040-1
+Power 30U-180HVIEC/EN 60950-1; IEC/EN 62040-1
+Power 42U-200-20KHVIEC/EN 60950-1; IEC/EN 62040-1
+Power 42U-210HVIEC/EN 60950-1; IEC/EN 62040-1
+Power 42U-300HVIEC/EN 60950-1; IEC/EN 62040-1
Brochure +Power_DS_Brochure
Manual +Power HV_20K_Manual
Manual +Power HV_30K_Manual
Manual +Power LV_20K_Manual
Related Products